APPENDIX B

FlexPak 3000

49’1340 e

B-30

MOP DECEL TIME (P.120)

Only available if the I/O Expansion kit is installed. Minimum time in which the MOP OUTPUT can change
from TOP SPEED to zero. See MOP ACCEL TIME for a discussion and block diagram.

Parameter Range:

DECELERATION TIME to 300.0 seconds

Default Setting:

5.0 seconds

Parameter Type:

Tuneable

OIM Menu Path(s):

Drive Reference - Drive Reference Ramp

Refer also to Parameters:

DECELERATION TIME (P.002),
MAXIMUM SPEED (P.004),
MINIMUM SPEED (P.003),
MOP ACCEL TIME (P.115)
MOP OUTPUT (P.191),
MOP RESET ENABLE (P.116)
TOP SPEED (P.011)

MOP RESET ENABLE (P.116)

Determines if the MOP OUTPUT resets or stays at the present level when the drive stops.
When MOP RESET ENABLE is ON, the MOP output goes to MINIMUM SPEED when the drive stops.
If it is OFF, the MOP OUTPUT remains at its present level when the drive stops.
This parameter also affects the operation of the keypad reference, even if the I/O Expansion kit is not
installed. See MOP ACCEL TIME for discussion and block diagram.

Parameter Range:

OFF,

ON

Default Setting:

OFF

Parameter Type:

Configurable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

Refer also to Parameters:

MINIMUM SPEED (P.003),
MOP ACCEL TIME (P.115),
MOP DECEL TIME (P.120),
MOP OUTPUT (P.191)

MOTOR HOT FLD AMPS (P.510)

Only available if the Field Current Regulator kit is installed.
Motor nameplate value of the rated hot field amps. This parameter scales the field current feedback.

Parameter Range:

0.1 to installed supply rating (4.00,10.00, or 15.00 amps)

Default Setting:

0.1 amps

Parameter Type:

Configurable

OIM Menu Path(s):

Field - Field Current Regulator - Field Loop Feedback Scaling

Refer also to Parameters:

FIELD ECONOMY REF (P.511),
FIELD FEEDBACK (P.589),
FIELD LOSS THRESHOLD (P.512),
FIELD REF REGISTER (P.513),
FLD FEEDBACK GAIN ADJ (P.516),

MOTOR HOT FLD AMPS (P.510)

WARNING:

The incorrect setting of this parameter can cause a motor overvoltage condition.

Set MOTOR HOT FLD AMPS to the motor's nameplate value. Make sure FIELD ECONOMY REF

and/or FIELD REF REGISTER (P.513) is above FIELD LOSS THRESHOLD (P.512).

Failure to observe this precaution can result in bodily injury and damage to the equipment.