APPENDIX E

49’1340 e

FlexPak 3000

E-3

Table E.1 - Fault Codes (Continued)

CODE

DISPLAY

DESCRIPTION

F00006 BLOWER MOTOR

STARTER OPEN

This fault is not applicable on European versions FlexPak 3000.

F00007 OPEN ARMATURE The motor armature circuit is open.

Possible causes:

Motor armature winding not connected or open circuit.

Blown inverting fault (DC) fuse.

Excessive armature voltage at motor speeds <5% of TOP SPEED,

Refer to Appendix B, TACH LOSS SCR ANGLE (P608).

F00008

MOTOR
THERMOSTAT TRIP

Motor thermostat indicates high temperature. If a motor thermostat is
not used, customer terminal board pins 13 and 14 must be jumpered to
inhibit this fault.
Possible causes:

Damaged or disconnected motor thermostat wiring.

Inadequate ventilation.

Blower motor failure.

Incorrect blower rotation.

Blocked ventilation slots.

Clogged filters.

Excessive armature current.

One or more thyristors not operating.

F00009

CONTROLLER
THERMOSTAT TRIP

Controller thermostat indicates high temperature.
Possible causes:

Inadequate heat sink ventilation.

Inadequate cabinet ventilation.

Heat sink fan failure.

Damaged or disconnected controller thermostat wiring.

F00010

AC LINE
SYNCHRONIZATION
FAULT

Three-phase AC line synchronization circuit failure.
Possible causes:

Blown AC line fuse(s).

AC line frequency not within required range of 48-62Hz.

Excessive AC line noise or distortion.

Unstable AC line frequency.

Disconnected, loosely connected or damaged J6 ribbon cable.

F00011

OIM
COMMUNICATIONS
TIMEOUT

The regulator board was unable to communicate with the Operator
Interface Module (OIM). (Refer to section 7.7.5 which discusses the
regulator status LEDs that can pinpoint whether or not the OIM is
communicating)
Possible causes:

Disconnected, loosely connected, or damaged OIM cable.

OIM failure.

Regulator board failure.

F00012

ARMATURE OVER
VOLTAGE

Armature voltage exceeded 130% of

MOTOR RATED ARM VOLTS (P.009)

.

Possible causes:

MOTOR RATED ARM VOLTS

not set properly.

Improper voltage loop tuning.

ENHANCED FLD VOLT ADJ

(P.500)

set too high (Enhanced Field

Supply kit only).