APPENDIX B

FlexPak 3000

49’1340 e

B-42

PHASE FIRE TST BRIDGE (P.310)

Armature phase fire test mode bridge select. This input can only be changed while the drive is stopped.
OFF selects the forward bridge (A1 positive with respect to A2).
ON selects the reverse bridge (A1 negative with respect to A2).

Parameter Range:

ON

OFF

Default Setting:

OFF

Parameter Type:

Tuneable

OIM Menu Path(s):

Current Minor Loop (CML) - SCR Diagnostics Armature Phase Fire Test

PLL MAXIMUM ERROR (P.308)
Maximum allowable change in line period per A-C line cycle.
This input should only be increased when drive power is supplied by a source that cannot maintain a
suitable fixed frequency output (such as an alternator) to prevent line synchronization-related faults.

Parameter Range:

2 to 1000 microsec

Default Setting:

2 microsec

Parameter Type:

Tuneable

OIM Menu Path(s):

Current Minor Loop (CML) - Three Phase AC Line

PHASE LOSS DETECT EN (P.609) (not available in SW-version 4.1)

Enables or disables the phase loss fault detection. When set to ENABLE, a “PHASE LOSS” fault
(F.00016) will be generated when the measured AC line voltage drops below 75% of the value specified
by NOMINAL AC LINE VOLTS (P.307) for more than 2 seconds.

Parameter Range:

DISABLE, ENABLE

Default Setting:

ENABLE

Parameter Type:

Boolean input, retentive, configurable

OIM Menu Path(s):

Additional Parameters

POS CURRENT LIM SEL (P.223)
Selects the source for the positive current limit.
If REGISTER is selected, the reference is POSITIVE CURRENT LIM (P.005).
The I/O Expansion kit must be installed to use ANALOG IN 1 (terminals 50 and 51 on the I/O Expansion
board), ANALOG IN 2 (terminals 52 and 53), or FREQUENCY IN (terminals 39, 40, and 41).
The AutoMax Network Communication board must be installed and CONTROL SOURCE SELECT must
be set to NETWORK to select the communication registers (NETW IN REG 1, 2, or 3).

Parameter Range:

REGISTER,

ANALOG IN 1,

ANALOG IN 2,

NETW IN REG 1,

NETW IN REG 2,

NETW IN REG 3

Default Setting:

REGISTER

Parameter Type:

Configurable

OIM Menu Path(s):

Speed/Voltage Loop (SPD) - Speed/Voltage Loop (SPD) Tuning
or Current Minor Loop (CML) - CML Tuning

Refer also to Parameters:

CONTROL SOURCE SELECT (P.000),
POSITIVE CURRENT LIM (P.005)