APPENDIX B

49’1340 e

FlexPak 3000

B-27

METER OUT 1 SELECT (P.404)

Selects the drive testpoint that will source meter output 1 (terminals 24 and 25 on the regulator board).

Parameter Range:

See table below for parameter options.

Default Setting:

CML FEEDBACK

Parameter Type:

Tuneable

OIM Menu Path(s):

Input/Output - Meter Outputs

Signal Selected

Full Scale Value

CML FEEDBACK (P.397)
CML REFERENCE (P.396)
CML ERROR (P.398)
SPD LOOP OUTPUT (P.299)

±

MOTOR RATED ARM AMPS * MAXIMUM CURRENT

100

SPD LOOP FEEDBACK (P.296)
SPD LOOP REFERENCE (P.295)
SPD LOOP ERROR (P.297)
SPEED RAMP OUTPUT (P.199)
SPEED RAMP INPUT TP (P.198)
SPD SOURCE SELECT OUT (P.193)
TRIM OUTPUT (P.197)
ANALOG TACH FEEDBACK (P.291)
PULSE TACH FEEDBACK (P.292)
OCL OUTPUT (P.848)

±

TOP SPEED

ARMATURE VOLTAGE (P.289)

±

MOTOR RATED ARM VOLTS

POWER OUTPUT

±

MOTOR RATED ARM VOLTS * MOTOR RATED ARM AMPS * MAXIMUM

CURRENT

100

FIELD REFERENCE (P.590)
FIELD FEEDBACK (P.589)

MOTOR HOT FLD AMPS

OCL REFERENCE (P.845)

±

4095

OCL RAMP OUTPUT (P.846)
OCL FEEDBACK (P.847)
NETW IN REG 1 (P.905)
NETW IN REG 2 (P.906)
NETW IN REG 3 (P.907)
FULL SCALE
ZERO

0

METER OUT 1 ZERO ADJ (P.402)

Removes any hardware-introduced offset from the Meter 1 output signal at the regulator board terminals.

Parameter Range:

-200 to + 200

Default Setting:

0

Parameter Type:

Tuneable

OIM Menu Path(s):

Input/Output - Meter Outputs

NOTE: Testpoint METER OUT ZERO must source METER OUT 1 SELECT for an accurate adjustment. See Appendix D,

figure D.8, for further details.