APPENDIX B

49’1340 e

FlexPak 3000

B-31

(FIELD FEEDBACK)

Scaling

Software

MOTOR HOT FLD AMPS

A/D

FIELD ECONOMY REF

100

MOTOR HOT FLD AMPS

MOTOR HOT FLD AMPS

FIELD REF REGISTER

MUL DIV

GAIN

LO

0

HI

FLD FEEDBACK

GAIN

GAIN ADJ

MUL

(FIELD ECONOMY ACTIVE)

ON

OFF

(FIELD REFERENCE)

FEEDBACK

FIELD CURRENT

To Field Current Regulator

Control Loop

P.510

P.599

P.590

P.589

P.511

P.510

P.513

P.516

P.510

+

-

MOTOR RATED ARM AMPS (P.008)

The rated armature current from the motor nameplate.

Parameter Range:

0 to 3000.0 Amps

Default Setting:

Depending on unit type

Parameter Type:

Configurable

OIM Menu Path(s):

Current Minor Loop (CML) - CML Feedback Scaling - Quick Start

CAUTION:

The drive will not operate properly if this parameter value is entered incorrectly. This parameter must

be equal to the rated armature amps found on the motor nameplate. Overcurrent or excess heating of

the motor could result. Failure to observe this precaution could result in damage to, or destruction of,

the equipment.

MOTOR RATED ARM VOLTS (P.009)

Rated armature voltage from the motor nameplate.

Parameter Range:

160 to 675 VDC on types with nominal voltage up to 500 VAC
240 to 1000 VDC on types with nominal voltage 690 VAC (see 4.5.11)

Default Setting:

240 VDC

Parameter Type:

Configurable

OIM Menu Path(s):

Speed/Voltage Loop (SPD) - Speed/Volt Loop (SPD) Feedback -Quick Start

Refer also to Parameter:

NOMINAL AC LINE VOLTS (P.307)

WARNING

The incorrect setting of this parameter can cause an overspeed condition. This parameter must be set

by a qualified person who understands the significance of setting it. Set the value of this parameter

accurately per your application requirements. Failure to observe this precaution could result in bodily

injury.