Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual

Page 79

Advertising
background image

TROUBLESHOOTING/DIAGNOSTICS

49’1340 e

FlexPak 3000

7-7

7.7.6

Armature Phase Fire Test

ATTENTION: Only qualified electrical personnel familiar with the construction and operation of this

equipment and the hazards involved should perform this test. Read and understand

this section in its entirety before proceeding.

Failure to observe this precaution could result in severe bodily injury or loss of life.

ATTENTION: This is an open loop test. To prevent excess motor speed and current, lock the motor

shaft or disconnect the motor armature leads from the drive and replace them with a

dummy load (e.g. bulbs in series).

Failure to observe this precaution could result in severe bodily injury or loss of life.

An armature phase fire test mode is available to verify the operation of the S6 or S6R rectifier
bridge. This test should only be performed by qualified personnel. Note that this test is not
available through the

DCM

.

To perform an armature phase fire test:

1. Turn off power to the drive. (Lockout and tag power as necessary).

2. Either lock the motor armature to prevent rotation or disconnect the motor armature leads

from the drive and replace with bulbs in series.
When locking the motor armature, the motor field winding can be disconnected to prevent
excessive torque. If the motor field winding is disconnected field current loss faults must be
inhibited by either setting jumper J20 to

DISABLE

on FlexPak with field rectifier or setting

Parameter

FIELD LOSS THRESHOLD

(P.512) to 0 on FlexPak with field current regulator.

3. Turn on power to the drive. The drive must be stopped and the Drive Ready Indicator must

be

ON

.

4. Set

CONTROL SOURCE SELECT

to

KEYPAD

.

5. On the

OIM

, select Current Minor Loop (

CML

) –

SCR

Diagnostics – Armature Phase Fire Test.

6. Set

PHASE FIRE TST BRIDGE

(P.310). This parameter must be set to the appropriate value

before activating the armature phase fire test mode.

7. Attach an oscilloscope to the armature current feedback test point (J17+, J22– on the

Regulator board). Note that the CS3000 software oscilloscope mode does not have
sufficient bandwidth for this test.

8. Press RUN. The armature phase fire test mode is now active. The

OIM

Running indicator will

be on.

9. Set

PHASE FIRE TEST DELTA

(P.309) to 55 degrees. Slowly increase

PHASE FIRE TEST DELTA

until a steady pattern of “bumps” appears on the oscilloscope. If all thyristors in the selected
bridge are operating, there will be six bumps per AC line cycle. If any bumps are missing,
one or more thyristors are not conducting.
Note that conduction will not begin until the firing angle is sufficiently advanced (

PHASE FIRE

TEST DELTA

(P.309) more than 60 degrees). A rate limit block limits the rate of change of

firing angle advances to prevent sudden increases in current. To prevent the drive from
entering continuous conduction during this test,

PHASE FIRE TEST DELTA

(P.309) should not

exceed 89 degrees.

10. Press STOP to stop the armature phase fire test.

11. Turn off power to the drive (lockout and tag as necessary).

12. Either unlock the motor armature or remove the bulbs and reconnect the motor armature

leads.

If the motor field winding was disconnected, reconnect it and return jumper J20 to its original
position (typically

ENABLE

on FlexPak with field rectifier) or (on FlexPak with field current

regulator) set parameter

FIELD LOSS THRESHOLD

(P.512) to its original value.

Advertising