Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual

Page 158

Advertising
background image

APPENDIX C

FlexPak 3000

49’1340 e

C-2

ANLG IN 1 (P.492)

Only available if the I/O Expansion kit is installed.
The value representing analog input 1 (terminals 50 and 51 on the I/O Expansion board) after gain and
zero have been applied. See ANLG IN 1 GAIN ADJ for block diagram.

OIM Menu Path(s):

Input/Output - Analog I/O

Refer also to Parameters:

ANLG IN 1 SIG TYPE (P.413),
ANLG IN 1 ZERO ADJ (P.414)
ANLG IN 1 GAIN ADJ (P.415)

ANLG IN 2 (P.493)

Only available if the I/O Expansion kit is installed.
The value representing analog input 2 (terminals 52 and 53 on the I/O Expansion board) after gain and
zero have been applied.

OIM Menu Path(s):

Input/Output - Analog I/O

Refer also to Parameters:

ANLG IN 2 GAIN ADJ (P.417),
ANLG IN 2 ZERO ADJ (P.416)

ARMATURE BRIDGE POL (P.394)

Indicates which bridge is currently active. OFF indicates the forward bridge; ON indicates the reverse
bridge.

OIM Menu Path(s):

Current Minor Loop (CML) - CML Test Points

ARMATURE DELTA (P.399)

Indicates the armature firing angle in microseconds.

OIM Menu Path(s):

Current Minor Loop (CML) - CML Test Points
Current Minor Loop (CML) - SCR Diagnostics
Armature Phase Fire Test

ARMATURE VOLTAGE (P.289)

Armature voltage value after all hardware and software scaling.

OIM Menu Path(s):

SPD - SPD Test Points,

SPD - SPD Feedback

Current Minor Loop (CML) -SCR Diagnostics - Armature Phase Fire Test

CML ERROR (P.398)

The CML error signal (i.e., the difference between CML REFERENCE and CML FEEDBACK).

OIM Menu Path(s):

Current Minor Loop (CML) - CML Test Points

CML FEEDBACK (P.397)

The CML feedback signal prior to the summing junction.

OIM Menu Path(s):

Current Minor Loop (CML) - SCR Diagnostics - Armature Phase Fire Test
Current Minor Loop (CML) - CML Feedback Scaling
Current Minor Loop (CML) - CML Test Points