QUICK START

49’1340 e

FlexPak 3000

6-3

ATTENTION:

The incorrect setting of the Quick Start parameters can cause an overspeed condition.

These parameters must be set by a qualified person who understands the significance of setting.

Verify that the value of these parameters is set accurately per your application requirements.

Failure to observe this precaution could result in bodily injury.

ATTENTION:

The parameter for the current transformer turns ratio (Tp/Tn) CT TURNS RATIO (P.010) is factory set

depending on the power unit size. Do not adjust/change the value of this parameter from its factory

default value unless you are replacing the regulator board without downloading of the parameter set. In

that case refer to Appendix B for setting the ratio (Tp/Tn).

Failure to observe this precaution could result in damage to, or destruction of, the equipment.

Table 6.2 - Quick Start Parameter Modification Sequence

Step
No.

Parameter
Name

Code
No.

Default

Description

User
Setting

1

TOP SPEED

011

500 RPM

The highest running speed of the motor. It
scales the feedback device.

TOP SPEED

depends on several factors:

If there is no field weakening, the top speed

is typically the same as the nameplate base
speed.

If there is field weakening, the Top Speed

is the same as the field weakened speed.
Top speed is typically more than the base
speed when field weakening is applied.

ATTENTION: Before starting the drive, this

parameter must be set to base speed or, if

the Field Current Regulator kit is installed,

the field weakened speed. You are

responsible for assuring safe conditions for

operating personnel by setting this

parameter properly. Failure to observe this

precaution could result in bodily injury.
Do not allow the motor to exceed the

maximum safe speed of the motor or driven

equipment as determined by the equipment

manufacturer. Failure to observe this

precaution can result in bodily injury

2

MOTOR
RATED ARM
AMPS

008

8 AMPS

ATTENTION: The drive will not operate

properly if this parameter value is wrong.

This parameter must be less than the rated

armature amps on the motor nameplate.

Failure to observe this precaution could

result in damage to, or destruction of, the

equipment.

The rated armature current from the motor
nameplate.