QUICK START

FlexPak 3000

49’1340 e

6-10

The following screen shows how the display will look after self-tuning has completed
successfully for both the CML and the SPD/Voltage Loop.

NOTE: The gains are not automatically saved to retentive memory. If the gain values are
acceptable, the user must perform a memory save.

Self Tuning
CML Tuning complete.
SPD/VOLTAGE Loop Tuning complete.
Self Tuning has updated the gains.
Press CANCEL to continue.

!!
!!

Fault
Alarm
Interlock OK
Drive Ready
Running
Current Limit
Torque Limit

PROGRAM

KEYPAD MANUAL FORWARD

Pressing CANCEL goes to the FlexPak 3000 Main Menu or to the previous screen if not
initiated as part of the Quick Start menu.

6.5

Final Adjustments

These adjustments detail how to adjust the nominal AC Line frequency and A-C line volts
parameters.

6.5.1

Nominal AC Line Adjustments

The frequency (NOMINAL A-C LINE FREQ, P.306) and the voltage (NOMINAL A-C LINE
VOLTS, P.307) adjustments are accessed by selecting Current Minor Loop (CML) at the Main
Menu and then selecting the Three-Phase AC Line at the CML menu level.

Current Minor Loop (CML)

- Three-Phase AC Line*

6.5.1.1 Perform Nominal AC Line Frequency Adjust

The default value is 50 Hz. Typically, the value is 50 or 60 Hz. Use the up/down arrow keys to
adjust the value to the nominal value of the line frequency in use. Valid values are 48 to 62 Hz.

6.5.1.2 Perform Nominal AC Line Volts Adjust

The default value is 400 VAC. Use the up/down arrow keys to adjust the value to the nominal
value of the AC line RMS voltage in use. Refer to Parameter description in Appendix B.