APPENDIX B

FlexPak 3000

49’1340 e

B-22

INV FAULT AVOID SEL

(P.312) settings and action taken when drive detects conditions that could lead to

an inverting fault.

Parameter Setting

Is Drive

Regenerating or

Attempting to

Regenerate?

Drive Action

DISABLED

n/a

None

FAULT
IMMEDIATELY

Yes

immediately stops (coast/DB)

generates the fault F00015 (

INVERTING FAULT AVOIDED).

FAULT
IMMEDIATELY

No (drive is

motoring)

generates the alarm A00005 (

INVERTING FAULT AVOIDED)

.

continues normal operation on the motoring bridge until a

request to regenerate is detected.

When a request to regenerate is detected, the drive immediately

stops (coast/DB) and generates the fault F00015 (INVERTING
FAULT AVOIDED)

DELAY BEFORE
FAULT

Yes

Immediately forces the Current Minor Loop reference to zero

Logs the alarm A0005 (

INVERTING FAULT AVOIDED)

Continues to operate normally for up to two seconds. The drive

can generate a motoring current as needed but will coast while a
demand for regenerative current exists.

If the demand for regenerative current persists for more than

two seconds, the drive:
- stops (coast/DB) and
- generates the fault F00015 (

INVERTING FAULT AVOIDED).

If the conditions that caused the alarm return to normal within

two seconds, the drive returns to normal operation (the
regenerative bridge will be re-enabled) without stopping.

DELAY BEFORE
FAULT

No (drive is

motoring)

Logs the alarm A0005 (

INVERTING FAULT AVOIDED).

Continues normal operation on the motoring bridge until a

request to regenerate is detected.

When a request to regenerate is detected, the drive continues to

operate normally for up to two seconds. The drive can generate a
motoring current as needed but will coast while a demand for
regenerative current exists.

If the demand for regenerative current persists for approximately

two seconds, the drive:
- stops (coast/DB)
- generates the fault F00015 (

INVERTING FAULT AVOIDED).

If the conditions that caused the alarm return to normal within

two seconds, the drive returns to normal operation (the
regenerative bridge will be re-enabled) without stopping.

IR COMPENSATION (P.206)

Sets the armature voltage loss compensation value used when the drive is configured as a voltage
regulator. This parameter is also used by the field current regulator to set the field weakened threshold.

Parameter Range:

0 to 50% of MOTOR RATED ARM AMPS (P.008)

Default Setting:

0%

Parameter Type:

Tuneable

OIM Menu Path(s):

Speed/Voltage Loop (SPD) - Spd/Volt Loop (SPD) Tuning - Quick Start
Field - Field Current Regulator - Field Loop Tuning