QUICK START

49’1340 e

FlexPak 3000

6-5

Table 6.2 - Quick Start Parameter Modification Sequence. - continued

Step
No.

Parameter
Name

Code
No.

Default

Description

User
Setting

9

ACCELERA-
TION RATE

001

5 SEC.

The time it takes to accelerate from 0 to Top
speed. Smaller changes in speed take
proportionately less time. If

TRIM MODE

SELECT

is set to

PROPORTIONAL

, this time

value is modified by

DRAW PERCENTAGE

OUT.

10

DECELERA-
TION RATE

002

5 SEC.

DECELERATION TIME

selects the time it takes

to decelerate from Top speed to 0. Smaller
changes in speed take proportionately less
time. If

TRIM MODE SELECT

is set to

PROPORTIONAL

, this time value is modified by

DRAW PERCENTAGE OUT.

11

MINIMUM
SPEED

003

0 RPM

ATTENTION: This drive can operate at and

maintaining zero speed when this parameter

is set to zero. The user is responsible for

assuring safe conditions for operating

personnel by providing suitable guards,

audible or visual alarms, or other devices to

indicate that the drive is operating at or near

zero speed. Failure to observe this

precaution could result in severe bodily injury

or loss of life.

Selects the minimum speed of the drive
without being stopped. It is typically greater
than zero. If it is < 10% of MAXIMUM SPEED,
an alarm is generated.

12

MAXIMUM
SPEED

004

500 RPM

The maximum speed of the drive that can be
supported by the application or process.
If raising this value causes

MINIMUM SPEED

to

become less than 10% of

MAXIMUM

SPEED

,

an alarm is generated.
This is typically set to base speed from the
motor nameplate.

ATTENTION: Do not allow the motor to

exceed the maximum safe speed as

determined by the equipment manufacturer

of the motor or the driven equipment.

Failure to observe these precautions could

result in bodily injury.

13

JOG ACCEL/
DECEL RATE

013

3 SEC.

The time it takes the Jog reference circuit to
reach

TOP SPEED (P.011)

from zero. The

S-

CURVE ROUNDING (P.014)

parameter does not

affect the setting of this parameter.