APPENDIX B

49’1340 e

FlexPak 3000

B-37

OCL FEEDBACK SELECT (P.804)

Selects the source for the outer control loop (OCL) feedback signal. The I/O Expansion kit must be
installed to use ANALOG IN 1, or ANALOG IN 2. An AutoMax network module must be installed and
CONTROL SOURCE SEL = NETWORK to access Selections 5 to 9.

Parameter Range:

NONE,

CML FEEDBACK,

ANALOG IN 1,

ANALOG IN 2

5 = SPEED LOOP OUTPUT,
6 = ANALOG AUTO REFERENCE
7 = NETW IN REG 1 (not available in SW-version 4.1)
8 = NETW IN REG 2 (not available in SW-version 4.1)
9 = NETW IN REG 3 (not available in SW-version 4.1)

Default Setting:

NONE

Parameter Type:

Enumerated input, configurable, retentive

OIM Menu Path(s):

Outer Control Loop (OCL) - OCL Configure

Refer also to Parameters:

CML FEEDBACK (P.397)

OCL LEADLAG LOW FREQ (P.806)

Lead/lag low break frequency of the outer control loop. Sets the lead break frequency if OCL LEADLAG
SELECT (P.807) is set to LEAD/LAG. Sets the lag break frequency if P.807 is set to LAG/LEAD.

Parameter Range:

0.01 to 34.90 RAD/S

Default Setting:

1.00 RAD/S

Parameter Type:

Tuneable

OIM Menu Path(s):

Outer Control Loop (OCL) - OCL Tuning

Refer also to Parameters:

OCL LEADLAG RATIO (P.807)
OCL LEADLAG SELECT (P.805)

The OCL lead/lag high break frequency is determined by the settings of this parameter and the OCL
LEADLAG RATIO. For example, if the low break frequency is 0.50 rad/s and the ratio is 10, the high
break frequency is 5.00 rad/s.

To Outer Control Loop

Block Diagram

OCL

FEEDBACK

SELECT

OCL

LEADLAG

SELECT

output of OCL

enable logic

OCL

LEADLAG

RATIO

OCL

LEADLAG

LOW FREQ

(O CL FEEDBACK)

CML FEEDBACK

ANALOG IN 1

ANALOG IN 2

From I/O Expansion

Inputs Block Diagram

(CML FEEDBACK)

8 sample average

{

*NONE

P.804

P.847

P.806

P.807

P.805

(A)

(B)

AUTO REF.

SPD LOOP OUTPUT

SPD LOOP OUTPUT 3)

ANALOG AUTO REFERENCE 3)

LEAD/LAG

* BYPASS

LAG/LEAD

INITV

L / L

WLD RST\ RATIO

OCL LEADLAG RATIO (P.807)

The ratio between the low break frequency and high break frequency of outer control loop lead/lag.
The settings of this parameter and the OCL LEADLAG LOW FREQ determine the high break frequency.
See OCL LEADLAG LOW FREQ for discussion and block diagram.

Parameter Range:

2 to 20

Default Setting:

10

Parameter Type:

Tuneable

OIM Menu Path(s):

Outer Control Loop (OCL) - OCL Tuning

Refer also to Parameters:

OCL LEADLAG LOW FREQ (P.806),
OCL LEADLAG SELECT (P.805)