Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual

Page 153

Advertising
background image

APPENDIX B

49’1340 e

FlexPak 3000

B-49

Ramp Stop

Command

0

On

Off

DEC

ACC

SCURVE

SMOOTHING

DECELERATION TIME

TRIM MODE SELECT

PROPORTIONAL

INCREMENTAL

* NO TRIM

DECEL TIME

----------------------------

1 + DRAW PERCENT

P.002

RATE

RAMP STOP DECEL TIME

TRIM MODE SELECT

PROPORTIONAL

INCREMENTAL

* NO TRIM

RAMP STOP DEC. T.

----------------------------

1 + DRAW PERCENT

P.110

P.110

P.018

Ramp Stop

Command

On

Off

STOP DECEL
SELECT

RAMP STOP DECEL TIME

* DECELERATION TIME

IV

RST

P.122

P.014
S-CURVE ROUNDING

STOP MODE SELECT (P.114)

Selects stopping mode of the drive in response to a normal STOP command. An open permissive will
always cause a coast stop. If the drive is configured as a current regulator, only COAST/DB can be
selected.

Parameter Range:

RAMP,
COAST/DB,
CURRENT LIMIT

Default Setting:

RAMP

Parameter Type:

Tuneable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

STOP SPEED THRESHOLD (P.113)

Sets the threshold speed below which the main contactor will automatically open after a ramp stop or
current limit stop is asserted. This value should be less than or equal to MINIMUM SPEED.

Parameter Range:

0 to MAXIMUM SPEED (RPM or user-defined units)

Default Setting:

0 (RPM or user-defined units)

Parameter Type:

Tuneable

OIM Menu Path(s):

Drive Reference - Drive Reference Configure

TACH LEAD FLT DELAY (P.228)

The amount of time that parameter TACH LEAD FLT THRESH (P.227) must be exceeded before a
REVERSED TACH LEADS fault (F00014) is generated.

Parameter Range:

0 to 32767 msec

Default Setting:

10 000 msec

Parameter Type:

Tuneable

OIM Menu Path(s):

Additional Parameters

Refer also to Parameters:

TACH LEAD FLT THRESH (P.227)