Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual

Page 128

Advertising
background image

APPENDIX B

FlexPak 3000

49’1340 e

B-24

LEVEL DETECT 1 DELAY (P.604)

The delay time in seconds for the level detector 1 circuit. Sets the amount of time between when the
level detector timer is triggered and when the output is set on. If the input source signal goes below the
detector's threshold value, the timer is immediately reset. See LEVEL DETECT 1 SELECT for diagram.
Parameter Range:

0.0 to 300.0 seconds

Default Setting:

10.0 seconds

Parameter Type:

Tuneable

OIM Menu Path(s):

Input/Output - Level Detectors

Refer also to Parameters:

DIG OUT 1 SELECT (P.409),
DIG OUT 2 SELECT (P.411)
LEVEL DETECT 1 OUTPUT (P.648),
LEVEL DETECT 1 SELECT (P.602)
LEVEL DETECT 1 THRESH (P.603)

LEVEL DETECT 1 SELECT (P.602)

Selects the signal that drives level detector 1.
Parameter Range:

SPD SOURCE SELECT OUT,

SPEED RAMP INPUT TP,

SPEED RAMP OUTPUT,

SPD LOOP FEEDBACK,

CML FEEDBACK

Default Setting:

SPD LOOP FEEDBACK

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Level Detectors

Refer also to Parameters:

LEVEL DETECT 1 THRESH (P.603),
LEVEL DETECT 1 DELAY (P.604),
LEVEL DETECT 1 OUTPUT (P.648)

LEVEL DETECT 1 THRESH (P.603)
The threshold for level detector 1. See LEVEL DETECT 1 SELECT for block diagram.
When the absolute value of the signal driving level detector 1 is greater than or equal to this threshold,
the associated timer starts. If the input signal is less than this threshold, the timer is immediately reset
and the level detector output is set to off.
Parameter Range:

0.1 to 100.0% or MAXIMUM CURRENT %*

Default Setting:

10.0%

Parameter Type:

Tuneable

OIM Menu Path(s):

Input/Output - Level Detectors

Refer also to Parameters:

LEVEL DETECT 1 DELAY (P.604), LEVEL DETECT 1 OUTPUT (P.648),
LEVEL DETECT 1 SELECT (P.602), MAXIMUM CURRENT (P.007)

*The parameter range for the level detector is automatically rescaled for speed or current based on the
input selected by LEVEL DETECT 1 SELECT. If CML FEEDBACK is selected for LEVEL DETECT 1
SELECT, the parameter range is 0.1 to MAXIMUM CURRENT. For any other LEVEL DETECT 1
SELECT settings, the parameter range is 0.1 to 100.0%.

LEVEL DETECT 2 DELAY (P.607)
The delay time in seconds for the level detector 2 circuit. See LEVEL DETECT 1 SELECT for diagram.
Parameter Range:

0.0 to 300.0 seconds

Default Setting:

10.0 seconds

Parameter Type:

Tuneable

OIM Menu Path(s):

Input/Output - Level Detectors

Refer also to Parameters:

LEVEL DETECT 1 SELECT (P.602), LEVEL DETECT 2 OUTPUT (P.649)
LEVEL DETECT 2 SELECT (P.605), LEVEL DETECT 2 THRESH (P.606)

Advertising