DIG OUT 1 CONTACT TYP (P.410)

Only available if the I/O Expansion Kit is installed. Selects whether digital output 1 (terminals 66 and 67
on I/O Expansion board) is normally open or normally closed.

Parameter Range:

NORMAL OPEN

NORMAL CLOSED

Default Setting:

NORMAL OPEN

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Digital I/O

Refer also to Parameters:

DIG OUT 1 SELECT (P.409)

If NORMAL OPEN is selected, digital output 1 is open when the signal is off and closed when it is on.
If NORMAL CLOSED is selected, digital output 1 is closed when the signal is off and open when on.

DANGER

On a power cycle or reset, the contact is held at normally open until the drive software is initialized.

Make sure that this condition does not result in a dangerous situation for your application. Failure to

observe this precaution can result in severe bodily injury or loss of life.

DIG OUT 1 SELECT (P.409)

Only available if the I/O Expansion Kit is installed. Selects the signal that drives digital output 1
(terminals 66 and 67 on the I/O Expansion board).

DANGER

This output is intended for use as an indication. If it is used as a control source, a dangerous condition

can result. Failure to observe this precaution can result in severe bodily injury or loss of life.

Parameter Range:

LEVEL DETECT 1 OUTPUT,

LEVEL DETECT 2 OUTPUT

IN CURRENT LIMIT,

DRIVE READY

NETW COMM STATUS,

NETW IN REG 1 (bit 0)

NETW IN REG 2 (bit 0),

NETW IN REG 3 (bit 0)

Default Setting:

LEVEL DETECT 1 OUTPUT

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Digital I/O

Refer also to Parameters:

LEVEL DETECT 1 OUTPUT (P.648),
LEVEL DETECT 2 OUTPUT (P.649)
NETW COMM STATUS (P.908), NETW IN REG 1 (P.905)
NETW IN REG 2 (P.906),

NETW IN REG 3 (P.907)

DIG OUT 2 CONTACT TYP (P.412)

Only available if the I/O Expansion Kit is installed. Selects whether digital output 2 (terminals 68 and 69
on the I/O Expansion board) is normally open or normally closed.

Parameter Range:

NORMAL OPEN,

NORMAL CLOSED

Default Setting:

NORMAL OPEN

Parameter Type:

Configurable

OIM Menu Path(s):

Input/Output - Digital I/O

Refer also to Parameters:

DIG OUT 2 SELECT (P.411)

If NORMAL OPEN is selected, digital output 2 is open when the signal is off and closed when it is on.
If NORMAL CLOSED is selected, digital output 2 is closed when the signal is off and open when it is on.

DANGER

On a power cycle or reset, the contact is held at normally open until the drive software is initialized.

Make sure that this condition does not result in a dangerous situation for your application. Failure to

observe this precaution can result in severe bodily injury or loss of life.