Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual

Page 203

Advertising
background image

APPENDIX G

49’1340 e

FlexPak 3000

G-3

Table G.1 - User Quick Reference Table for Input Parameters (continued)

Par.

Parameter

Parameter Selection /

Pg Initial Factory

User Data

No.

Adjustment Range

B-

Setting

Date

Setting

207

PULSE TACH PPR

18 - 2500 PPR

43

18 PPR

208

PULSE TACH QUADRATURE

OFF

ON

44

ON

209

CURRENT COMPOUNDING

-50% - +50%

11

0%

Speed Regulator Adjustm.

211

SPD LOOP PI PROP GAIN

0.10 - 128.00

48

4.40

212

SPD LOOP PI LEAD FREQ

0.00 to 282.74 rad/s if

FEEDBACK

SELECT = ARMATURE VOLT

0.00 to 327.67 rad/s if

FEEDBACK

SELECT

ARMATURE VOLT

47

3.00 rad/s

213

SPD LEADLAG RATIO

2 - 20

46

2

214

SPD LEADLAG LOW FREQ

0.01 - 34.90 rad/s

46

1.00 rad/s

215

SPD LOOP LAG FREQ

0.01 to 139.62 rad/s if

FEEDBACK

SELECT = ARMATURE VOLT

0.01 to 279.25 rad/s if

FEEDBACK

SELECT

ARMATURE VOLT

47

1.00 rad/s

216

SPD LEADLAG SELECT

LEAD/LAG

BYPASS

LAG/LEAD

46

BYPASS

217

SPD LOOP LAG BYPASS

OFF

ON

47

ON

Self Tuning Set-up

218

SELF TUNE FIELD RANGE

0.90 - 5.00

45

1.00

219

SELF TUNE STABILITY

10 - 100

45

25

220

SELF TUNE BRIDGE

FORWARD

REVERSE

45

FORWARD

221

INERTIA COMP SELECT

NONE

INTERNAL

ANALOG IN 1

ANALOG IN 2

NETW IN REG 1

NETW IN REG 2

NETW IN REG 3

21

NONE

222

NORMALIZED INERTIA

0.05 - 65.20 sec

36

1.00 sec

223

POS CURRENT LIM SEL

REGISTER

ANALOG IN 1

ANALOG IN 2

NETW IN REG 1

NETW IN REG 2

NETW IN REG 3

42

REGISTER

224

NEG CURRENT LIM SEL

REGISTER

ANALOG IN 1

ANALOG IN 2

NETW IN REG 1

NETW IN REG 2

NETW IN REG 3

32

REGISTER

226

NEG CUR LIM INV EN

1 = DISABLE

2 = ENABLE

32

2

227

TACH LEAD FLT THRESH

0.0 to 250 % (of TOP SPEED)

50

200.0

228

TACH LEAD FLT DELAY

0 to 32767 (msec)

49

10 000

Advertising