QUICK START

49’1340 e

FlexPak 3000

6-7

Step
No.

Parameter
Name

Code
No.

Default

Description

User
Setting

18

MOTOR HOT
FLD AMPS

510

0.01amps

This parameter only needs to be set if a field
current regulator is installed. Motor nameplate
value of the rated hot field amps. This input is
the basis of field current scaling.
If the factory defaults are restored, or if a valid
value has not yet been entered for this
parameter, the DC field voltage is fixed at
150V on a 230VAC line, or at 300V on a
460VAC line.

ATTENTION You must configure this to the

motor nameplate value. The incorrect

configuration of this parameter can cause a

motor overvoltage condition. Configure

MOTOR HOT FLD AMPS

to the motor’s

nameplate value. Failure to observe this

precaution can result in bodily injury and

damage to the equipment

19

Jumper
Informat.
Display

J11

J14

792

793

N/A

ATTENTION: The drive will not operate at

the correct speed if these jumpers are not

set to the correct positions. Set these

jumpers to the positions as displayed in the

"Quick Start" procedure for the drive to

operate at the correct speed.

Failure to observe this precaution could

result in damage to, or destruction of, the

equipment.

J11

J14

J18 395

The OIM displays the correct jumper positions
for J11, J14 and J18. Record these positions
in the space provided. Verify that the hardware
for these jumpers is positioned the same
before continuing with Quick Start.

J18

20

Self
Tune?
NO
YES

N/A N/A

N/A

NO - Returns the display to the Main Menu.
Perform a memory save to store values to
retentive memory.
YES - Proceeds with the Self-Tuning
procedure. Refer to the Self-Tuning section of
this instruction manual before proceeding with
self-tuning.

Not Re-
quired

N/A = Not Applicable.