APPENDIX B

49’1340 e

FlexPak 3000

B-39

OCL PI POSITIVE LIMIT (P.810)

Outer Control Loop PI block positive limit. The output of OCL PI block is never above this limit. See OCL
PI LEAD FREQ for the block diagram.

Parameter Range:

0 to 100% of TOP SPEED

Default Setting:

100%

Parameter Type:

Tuneable

OIM Menu Path(s):

Outer Control Loop (OCL) - OCL Tuning

Refer also to Parameters:

OCL OUTPUT (P.848),

OCL PI LEAD FREQ (P.809),

OCL PI NEGATIVE LIMIT (P.811),

OCL PI PROP GAIN (P.808),

OCL RAMP OUTPUT (P.846),

TOP SPEED (P.011)

OCL PI PROP GAIN (P.808)

The proportional gain of the OCL PI block. See OCL PI LEAD FREQ for the block diagram.

Parameter Range:

0.10 to 128.00

Default Setting:

2.00

Parameter Type:

Tuneable

OIM Menu Path(s):

Outer Control Loop (OCL) - OCL Tuning

Refer also to Parameters:

OCL OUTPUT (P.848),
OCL PI LEAD FREQ (P.809),
OCL PI NEGATIVE LIMIT (P.811),
OCL PI POSITIVE LIMIT (P.810),
OCL RAMP OUTPUT (P.846)

OCL PROP TRIM SELECT (P.813)

Selects whether or not the output of the Outer Control Loop will be scaled by the absolute value of
SPEED RAMP OUTPUT (output of the Speed Loop S-Curve block).

Parameter Range:

1= DISABLE
2= ENABLE

Default Setting:

1

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters

Refer also to Parameters:

OCL PI LEAD FREQ (P.809), TOP SPEED

(P.011)

If OCL PROP TRIM SELECT

is enabled, the signal from the trim range block is passed through another

gain block. The gain of this block is proportional to the absolute value of the speed reference at the
output of the speed loop S-curve block. The gain of this block ranges from 0 at zero speed to unity gain
when the reference is equal to TOP SPEED

(P.011).

OCL REF RAMP TIME (P.802)

The ramp time for the outer control loop reference. Sets the minimum amount of time for the OCL S-
curve output to change from 0 to full scale and vice versa. If set to 0.0, the ramp block is bypassed.
NOTE: If the ramp block is bypassed, rapid speed change can result.

Parameter Range:

0.0 to 300.0 seconds

Default Setting:

10.0 seconds

Parameter Type:

Tuneable

OIM Menu Path(s):

Outer Control Loop (OCL) - OCL Tuning

Refer also to Parameters:

OCL RAMP OUTPUT (P.846),
OCL REFERENCE (P.845),
OCL REF RAMP TIME (P.802),
OCL REF ROUNDING (P.803)