APPENDIX B

FlexPak 3000

49’1340 e

B-10

CML REF LIMIT SELECT (P.311)

Selects the source for the CML positive and negative current limits.

Parameter Range:

1 = SPD LOOP PI LIMITS
2 = REGISTER

Default Setting:

1

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters

See POSITIVE CURRENT LIM (P.005) and NEGATIVE CURRENT LIM (P.006)
for information regarding the operation of the current limit registers.

(SPD LOOP OUTPUT)

PI

KP HI

WLD LO

POSITIVE CURRENT LIM

POS CURRENT

LIM SEL

*REGISTER

ANALOG IN 1

ANALOG IN 2

NETW IN REG 1, 2, 3

From Network

From I/O Expansion

Inputs Block Diagram

{

P.005

P.299

P.223

NEGATIVE
CURRENT LIM

ANALOG IN 2

NETW IN REG 1, 2, 3

From Network

From I/O Expansion

Inputs Block Diagram

{

NEG CURRENT

LIM SEL

*REGISTER

ANALOG IN 1

EN

P.006

P.224

(A)

(B)

(B)

(A)

INIT

RST

SPEED LOOP

CURRENT LOOP

HI

LO

LIMIT

P.005

EN

NEG CURRENT LIM INV EN 3)

P.226

POS CURRENT LIM

* SPD LOOP CUR LIM

REGISTER

CML REF LIMIT
SELECT

P.311

* SPD LOOP CUR LIM

REGISTER

CML REF LIMIT SELECT

P.311

NEG CURRENT LIM

P.006

CML REF RATE LIMIT (P.303)

Minimum allowable time for selected CML reference to change from zero to MAXIMUM CURRENT.

Parameter Range:

1 to 1000 msec

Default Setting:

40 msec

Parameter Type:

Tuneable

OIM Menu Path(s):

Current Minor Loop (CML) - CML Tuning

CNI PROG/RUN MODE (P.915) (not available in SW-version 4.1)

CNI = ControlNet Interface (optional card). Selects how the drive responds when communicating with a
PLC while it is in program mode. The drive will not be ready while in the program mode if this parameter
is set to STOP.

Parameter Range:

1 = STOP,
2 = NOT STOP

Default Setting:

1 = STOP

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters