QUICK START

FlexPak 3000

49’1340 e

6-6

Table 6.2 - Quick Start Parameter Modification Sequence. – continued

Step
No.

Parameter
Name

Code
No.

Default

Description

User
Setting

14

JOG SPEED1 012

250 RPM

The operating speed when the drive is
jogging. If DIG IN 0 SELECT (P.428) is set to

JOG

SPEED SELECT

, this parameter is used

when

DIG IN 0

(terminal 12) is off.

ATTENTION: This drive can operate at and

maintaining zero speed when this

parameter is set to zero. The user is

responsible for assuring safe conditions for

operating personnel by providing suitable

guards, audible or visual alarms, or other

devices to indicate that the drive is

operating at or near zero speed. Failure to

observe this precaution could result in

severe bodily injury or loss of life.

15

POSITIVE
CURRENT
LIM

005

150% FLA

Sets the highest amount of current (% full load
amps) for the forward bridge. Used as a high
limit for the speed loop PI block when

POS

CURRENT LIM SEL (P.224)

is set to

REGISTER

.

16

NEGATIVE
CURRENT
LIM

006

150%
FLA

This parameter only needs to be set for
regenerative drives. Selects the highest
amount of current (% full load amps) for the
reverse bridge.
Used as a low limit for the speed loop

PI

block

when

NEG CURRENT LIM SEL

(P.224)

is set to

REGISTER

.

The range is clamped to zero:

For non-regenerative drives.

If

FEEDBACK SELECT

is set to

AC TACH

.

I

F FEEDBACK SELECT

is set to

PULSE TACH

and

PULSE TACH QUADRATURE

(P.208)

is set

to

OFF

.

The range depends on the setting of

NEG CUR

LIM INV EN

(P.226).

17

IR COMPEN-
SATION

206

0% FLA

Armature voltage loss compensation value
used when the drive is configured as a voltage
regulator. This parameter is also used by the
field current regulator to set the field
weakened threshold.

IR COMPENSATION

is normally determined from

the motor data sheet. It should be set to the
percent

IR

drop of the motor.

If this data is not available on the motor data
sheet, you can set this empirically so that the
no-load and full-load speeds are as close as
possible when operating as a voltage
regulator.
This parameter is not available for
current/torque regulated drives.

Table 6.2 - Quick Start Parameter Modification Sequence. – continued