Source select is changed from – Rockwell Automation FlexPak 3000 Power Module Version 4.2 User Manual

Page 156

Advertising
background image

APPENDIX B

FlexPak 3000

49’1340 e

B-52

UNDERWIND ENABLE (Alternate network map, Drop_1, register 32, Bit 5)

Setting this bit to 1 enables two inverter blocks that permit underwind operation.
Setting this bit to 0 disables the two inverter blocks and permits overwind operation.

Parameter Range:

0 = DISABLED (overwind)
1 = ENABLED (underwind)

Default Setting:

0

Parameter Type:

Configurable

OIM Menu Path(s):

This parameter is available over the network, alternate network map,
drop_1, register 32, bit 5. It cannot be viewed through the

OIM

or

DCM

.

The use this register, CONTROL SOURCE SELECT must be set to

NETWORK

and NETW REGISTER

MAP SEL (P.914) must be set to ALTERNATE

.

The inverters are added to the speed loop block and the current minor loop reference block.

ATTENTION:

If CONTROL SOURCE SELECT is changed from NETWORK to any other control source, the

UNDERWIND ENABLE

bit is forced to the default if DISABLED. If the setting was ENABLED and

CONTROL

SOURCE SELECT is changed from

NETWORK

, the motor rotates in the opposite direction

when the drive is restarted. The active speed reference should be set to zero before starting the drive

from the new control source. Slowly increase the speed reference until the proper rotation direction

can be determined. If it is incorrect, change the setting of the FORWARD/REVERSE input. The active

speed reference is based on the new control source and the AUTO/MANUAL setting.

From Speed Reference

Mode Select Block Diagram

(SPD LOOP REFERENCE)

SPD LOOP LAG FREQ

(SPD LOOP OUTPUT)

SPD LOOP

LAG BYPASS

(SPD LOOP ERROR)

WLG

LAG

(SPD LOOP

LAG OUTPUT)

PI

KP HI

WLD LO

To CML Reference

Block Diagram

+

D.5(E)

P.295

P.297

P.215

P.217

P.298

P.299

D.9(A)

A

B

A * B
1000

UNDERWIND ENABLE 1)
Netw. Drop 1, Reg. 32, Bit 5

SPEED FEEDBACK GAIN 1)
Netw. Drop 1, Reg. 38

INIT

RST

* BYPASS

ENABLE

OFF

*ON

Feedback Multiplier
Bypass 2)

EN

Advertising