APPENDIX B

FlexPak 3000

49’1340 e

B-36

NETW OUT REG 3 SELECT (P.904)

Selects which parameter is to be monitored in drop_1, register 9. Select the parameter to monitor by
programming the parameter number. For example, setting this parameter equal to 588 will write the
value of output parameter FIELD DELTA to register 9.

Parameter Range:

-32768 to 32767

Default Setting:

0

Parameter Type:

Tuneable

OIM Menu Path(s):

Network Communications

NETW REGISTER MAP SEL (P.914)

Only available if an AutoMax Network Communication Option board is installed.
Indicates which register map configuration will be used for the AutoMax Network Communic. board.

Parameter Range:

1 = ORIGINAL,
2 = ALTERNATE

Default Setting:

1

Parameter Type:

Configurable

OIM Menu Path(s):

Additional Parameters

The alternate map exchanges several registers between the Drop_1 area and other drops in addition to
a few new registers. The values displayed when using the AutoMax network are shown in brackets.

NOMINAL AC LINE FREQ (P.306)

The nominal A-C line frequency (typically 50 or 60 Hz).

Parameter Range:

48 to 62 Hz

Default Setting:

50

Parameter Type:

Configurable

OIM Menu Path(s):

Current Minor Loop (CML) - Three Phase AC Line

NOMINAL AC LINE VOLTS (P.307)

The nominal A-C line RMS voltage.

Parameter Range:

200 to 575 VAC on types with nominal voltage up to 500 VAC
300 to 850 VAC on types with nominal voltage 690 VAC (see 4.5.11)

Default Setting:

400 VAC

Parameter Type:

Configurable

OIM Menu Path(s):

Current Minor Loop (CML) - Three Phase AC Line

Refer also to Parameter:

MOTOR RATED ARM VOLTS (P.009)

NORMALIZED INERTIA (P.222)

The time required to accelerate the motor and load inertia from zero to motor base speed at MOTOR
RATED ARM AMPS and MOTOR HOT FLD AMPS.
This parameter is set by the speed loop self-tuning procedure or is entered by the operator directly.

Parameter Range:

0.05 to 65.20 seconds

Default Setting:

1.00 second

Parameter Type:

Tuneable

OIM Menu Path(s):

Speed/Voltage Loop (SPD) - Speed/Voltage Loop (SPD) Tuning

Refer also to Parameters:

INERTIA COMP SELECT (P.221),

MOTOR HOT FLD AMPS (P.510),

MOTOR RATED ARM AMPS (P.008)