OCL TYPE3 POSN REG EN (P.814) (not available in SW-version 4.1)

Selects the source of the Current Minor Loop reference when the drive is configured as a current
regulator (i.e. when hardware jumper J15 set to CURRENT). When OCL TYPE3 POSN REG EN set to
DISABLED, TORQUE REFERENCE (P.189) is used as the CML reference. When set to ENABLED,
OCL OUTPUT (P.848) is used as the CML reference.

Parameter Range:

1 = DISABLED
2 = ENABLED

Default Setting:

1 = DISABLED

Parameter Type:

Boolean input, retentive, configurable

OIM Menu Path(s):

Additional Parameters

OPEN SCR SENSITIVITY (P.600)

Open SCR diagnostic sensitivity adjustment. Unbalanced A-C lines can cause load sharing differences
between SCRs. This parameter should be increased to increase the tolerance of SCR load sharing
differences due to unbalanced lines.

Parameter Range:

0 to 100%

Default Setting:

0%

Parameter Type:

Tuneable

OIM Menu Path(s):

Current Minor Loop (CML) - SCR Diagnostics

OPEN SCR TRIP THRESH (P.601)

Open SCR trip threshold. Extremely unusual load conditions or severe current loop instability can cause
nuisance open SCR faults. Increasing this input will increase the tolerance of such disturbances.

Parameter Range:

800 to 4000

Default Setting:

800

Parameter Type:

Tuneable

OIM Menu Path(s):

Current Minor Loop (CML) - SCR Diagnostics

PHASE FIRE TEST DELTA (P.309)

The test firing conduction angle of the SCRs. If equal to 0, the armature power bridge is OFF.
If = 180, the armature power bridge is fully ON.

Parameter Range:

0 to 180 degrees

Default Setting:

0 degrees

Parameter Type:

Tuneable

OIM Menu Path(s):

Current Minor Loop (CML) - SCR Diagnostics

WARNING

The armature phase fire test is unregulated. To prevent excess motor speed, either disconnect the

armature leads from the drive and replace with a similar load or disconnect the field leads from the

drive. Lock the motor armature shaft securely to prevent rotation in either direction prior to selecting

this test. Failure to observe these precautions could result in bodily injury.