P5 to e7/p7 conversion tool table, Gpd5 conve ta table 1: parameter conversion – Yaskawa DriveWizard AC Drive User Manual

Page 140

Advertising
background image

G

PD5

Conve

Ta

Table 1: Parameter Conversion

PD

505/P5 to E7 and G

05/P5 to P7

rsion

bles

P5

Par.

P5 Parameter Name

Conversion

E7/P7

Par.

E7/P7 Parameter

Name

n001 Param selection/ init

NVERTED

NOT CO

NA

NA

n002

Op Mode Select

See Table 2

b1-01 &
b1-02

Run Seq Select
Ref Select

n003

Motor Rated Voltage

n003/10 = E1-01

E1-01

Input Voltage

n004

Stop Method

If n004 > 1, then b1-03 =3,
else n004 = b1-03

b1-03

Stopping Method

n005

Phase Rotation

n006

Reverse Prohibited

See Table 3

b1-04

Reverse operation

n007

Local/Remote

None

o2-01

Local / Remote Key

n008

Stop Key Function

o2-02

None

n009

Freq Ref Setting from
Digital Operator

If n009=1, then o2-05=0,

else o2-05 = 1

o2-05

Freq Ref Setting Method
Selection

n010

V/F Pattern Select

NOT CONVERTED

NA

NA

n011 Motor Rated Voltage

NOT CONVERTED

NA

NA

n012

Max Frequency

If n012 > 120.0 then E1-04
=120.0, else n012 = E1-04

E1-04

Max Output Freq.

n013

Max voltage

None

E1-05

Output Voltage

Max

n014

Base Frequency

If n014 > 200.0 then E1-06
=200.0, else n014 = E1-06

E1-06

Base Frequency

n015

Mid Frequency

If n015 > 200.0 then E1-07
=200.0, else n015 = E1-07

E1-07

Mid Frequency

n016

Mid voltage

None

E1-08

oltage A

Mid V

n017

Min Frequency

None

E1-09

Min Frequency

n018

Min Voltage

None

E1-10

ltage

Min Vo

n019

Accel Time 1

If n019 > 999.9, then
n019*10 = C1-01, else n019
= C1-01

C1-01

Acceleration Time 1

n020

Decel Time 1

If n020 > 999.9, then
n020*10 = C1-02, else n020
= C1-02

C1-02

Deceleration Time 1

n021

Accel Time 2

If n021 > 999.9, then n021
*10 = C1-03, else n021 =
C1-03

C1-03

Acceleration Time 2

n022

Decel Time 2

If n022 > 999.9, then
n022*10 = C1-04, n022 =
C1-04

C1-04

Deceleration Time 2

n023

S-curve select

NOT CONVERTED

NA

NA

n024

Operator Display Units

If n024 >39 then n024*10 =
o1-03, else n024 = o1-03

o1-03

Digital Operator Display
Selection

n025

Freq Reference #1

n025*10 = d1-01

d1-01

Frequency Reference 1

n026

Freq Reference #2

n026*10 = d1-02

d1-02

Frequency Reference 2

n027

Freq Reference #3

n027*10 = d1-03

d1-03

Frequency Reference 3

n028

Freq Reference #4

n028*10 = d1-04

d1-04

Frequency Reference 4

n029

Jog Reference

n029*10 = d1-17

d1-17

Jog Freq. reference

n030

Freq Ref Upper Limit

n030*10 = d2-01

d2-01

Freq Ref. Upper Limit

n031

Freq Ref Lower Limit

n031*10 = d2-02

d2-02

Freq. Ref. Lower Limit

n032

Motor Rated Current

None

E2-01

Motor Rated Current

140