P5+ to e7/p7 conversion tool tables – Yaskawa DriveWizard AC Drive User Manual

Page 145

Advertising
background image

GPD 50

d GPD

P7 C

sion Tables

Table 1: Parameter conversion

6/P5+ to E7 an

506/P5+ to

onver

P5+

Par.

P5+ Parameter

Name

Conversion

E7/P7

Par.

E7/P7 Parameter

Name

n001

it

Param selection/ in

NOT CONVERTED

NA

NA

n002

Op Mode Select

See Table 2

b1-01 &
b1-02

Run Seq Select
Ref Select

n003

Motor Rated Voltage

n003/10 = E1-01

E1-01

Input Voltage

n004

Stop Method

If n004 > 1, then b1-03
=3, else n004 = b1-03

b1-03

Stopping Method

n005

Phase Rotation

n006

Reverse Prohibited

See Table 3

b1-04

Reverse operation

n007

Local/Remote

None

o2-01

l / Remote Key

Loca

n008

Stop Key Function

None

o2-02

n009

Freq Ref Setting from
Digital Operator

If n009=1, then o2-05=0,
else o2-05 = 1

o2-05

Freq Ref Setting Method
Selection

n010

V/F Pattern Select

ONVERTED

NA

NOT C

NA

n011

Max Frequency

If n011 > 120.0 then E1-
04 =120.0, else n011 =
E1-04

E1-04

Max Output Freq.

n012

Max voltage

None

E1-05

Max Output Voltage

n013

Base Frequency

If n013 > 200.0 then E1-
06 =200.0, else n013 =
E1-06

E1-06

Base Frequency

n014

Mid Frequency

If n014 > 200.0 then E1-
07 =200.0, else n014 =
E1-07

E1-07

Mid Frequency

n015

Mid voltage

None

E1-08

Mid Voltage A

n016

Min Frequency

None

E1-09

Min Frequency

n017

Min V

Min Voltage

None

E1-10

oltage

n018

Accel Time 1

If n018 > 999.9, then
n018*10 = C1-01, else
n018 = C1-01

C1-01

Acceleration Time 1

n019

Decel Time 1

If n019 > 999.9, then
n018*10 = C1-02, else
n019 = C1-02

C1-02

Deceleration Time 1

n020

Accel Time 2

n020 *10 = C1-03

C1-03

Acceleration Time 2

n021

Decel Time 2

n021*10 = C1-04

C1-04

Deceleration Time 2

n022

S-curve select

NOT CONVERTED

NA

NA

n023

Operator Display Units

If n023 >39 then n023*10
= o1-03, else n023 = o1-
03

o1-03

Digital Operator Display
Selection

n024

Freq Reference #1

n025*10 = d1-01

d1-01

Frequency Reference 1

n025

Freq Reference #2

n026*10 = d1-02

d1-02

Frequency Reference 2

n026

Freq Reference #3

n027*10 = d1-03

d1-03

Frequency Reference 3

n027

Freq Reference #4

n028*10 = d1-04

d1-04

Frequency Reference 4

n028

D

Freq Reference #5

NOT CONVERTE

NA

NA

n029

Freq Reference #6

NOT CONVERTED

NA

NA

n030

Jog Reference

n030*10 = d1-17

d1-17

Jog Freq. reference

n031

Freq Ref Upper Limit

n031*10 = d2-01

d2-01

Freq Ref. Upper Limit

n032

Freq Ref Lower Limit

n032*10 = d2-02

d2-02

Freq. Ref. Lower Limit

145

Advertising