“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA) Units

Acc1 to Acc2 frequency

transition point

A095

ACC CHfr

0000.0Hz

Output frequency at which

Accel1 switches to Accel2, range

is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

Acc1 to Acc2 frequency

transition point, 2nd motor

A295

2ACCCHfr

0000.0Hz

Output frequency at which

Accel1 switches to Accel2, 2nd

motor, range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

Dec1 to Dec2 frequency
transition point

A096

DEC CHfr

0000.0Hz

Output frequency at which
Decel1 switches to Decel2, range

is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

Dec1 to Dec2 frequency

transition point, 2nd motor

A296

2DECCHfr

0000.0Hz

Output frequency at which

Decel1 switches to Decel2, 2nd

motor, range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

NOTE: For A095 and A096 (and for 2nd motor settings), if you set a very rapid Acc1 or
Dec1 time (less than 1.0 second), the inverter may not be able to change rates to Acc2 or
Dec2 before reaching the target frequency. In that case, the inverter decreases the rate

of Acc1 or Dec1 in order to achieve the second ramp to the target frequency.