B − 36 – Hitachi X200 Series User Manual

Page 263

Advertising
background image

The following table lists the holding registers for the “C” Group Intelligent Input Functions.

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

C001 Terminal [1] function

R/W

1103h

C201 Terminal [1] function,

2nd motor

R/W

1532h

C002 Terminal [2] function

R/W

1104h

C202 Terminal [2] function,

2nd motor

R/W

1533h

C003 Terminal [3] function

R/W

1105h

C203 Terminal [3] function,

2nd motor

R/W

1534h

C004 Terminal [4] function

R/W

1106h

C204 Terminal [4] function,

2nd motor

R/W

1535h

C005 Terminal [5] function

R/W

1107h

C205 Terminal [5] function,

2nd motor

R/W

See “Input Terminal Configuration”

on page 3-49

1536h

0, 1, 2, 3,

4, 5, 6, 7,

8, 9, 11,

12, 13,

15, 16,

18, 19,
20, 21,

22, 23,

24, 27,
28, 29,

31, 50,

51, 52,

53, 64,

255

C011 Terminal [1] active state R/W

110Bh

0, 1

C012 Terminal [2] active state R/W

110Ch

0, 1

C013 Terminal [3] active state R/W

110Dh

0, 1

C014 Terminal [4] active state R/W

110Eh

0, 1

C015 Terminal [5] active state R/W

Select logic conversion, two option

codes:
00

…normally open [NO]

01

…normally closed [NC]

110Fh

0, 1

C021 Terminal [11] function

R/W

1114h

C026 Alarm relay terminal

function

R/W

See “Output Terminal

Configuration” on page 3-54

1119h

0, 1, 2, 3,

4, 5, 6, 7,

8, 9, 10,

43

C028 [AM] signal selection

R/W Two available functions:

00

…motor speed

01

…motor current

111Bh

0, 1

C031 Terminal [11] active

state

R/W Select logic conversion:

00

…normally open [NO]

01

…normally closed [NC]

111Dh

0, 1

C036 Alarm relay active state

R/W Select logic conversion:

00

…normally open [NO]

01

…normally closed [NC]

1122h

0, 1

C038 Output mode of low load

detection signal

R/W Three option codes:

00

…Disabled

01

…During acceleration,

deceleration and constant speed

02

…During constant speed only

1178h

0, 1, 2

C039 Low load detection level

R/W Set the level of low load detection,

range is 0.0 to 2.0*rated current

1179h

0 to

20000

0.01%

C041 Overload level setting

R/W

1124h

C241 Overload level setting,

2nd motor

R/W

Sets the overload signal level
between 0% and 200% (from 0 to two

time the rated current of the

inverter)

153Ah

0 to

20000

0.01%

C042 Frequency arrival

setting for acceleration

R/W Sets the frequency arrival setting

threshold for the output frequency
during acceleration,

range is 0.0 to 400.0 Hz

1126h 0 to 4000

*1

0.1 Hz

C043 Frequency arrival

setting for deceleration

R/W Sets the frequency arrival setting

threshold for the output frequency

during deceleration,

range is 0.0 to 400.0 Hz

1128h 0 to 4000 0.1 Hz

B36

Appe

ndix B

Advertising