Sinking Outputs, Open Collector

The inverter has an internal relay output with

normally open and normally closed contacts
(Type 1 form C). The output signal that controls

the relay is configurable; the Alarm Signal is

the default setting. Thus, the terminals are
labeled [AL0], [AL1], [AL2], as shown to the

right. However, you can assign any one of the

nine intelligent outputs to the relay. For wiring
purposes, the general terminal function are:
• [AL0] – Common contact
• [AL1] – Normally open contact
• [AL2] – Normally closed contact

The relay itself can be configured as “normally open or closed.” Parameter C036, Alarm
Relay Active State, is the setting. This setting determines whether or not the relay coil

is energized when its output signal is OFF:
• C036=00 – “Normally open” (relay coil is de-energized when output signal is OFF)
• C036=01 – “Normally closed” (relay coil is energized when the output signal is OFF)

Since the relay already has normally open
[AL1] and normally closed [AL2] contacts, the

purpose of the ability to invert the relay coil’s

active state may not be obvious.

It allows you to

determine whether or not an inverter power

loss causes the relay to change state.

The

default relay configuration is the Alarm Signal
(C026=05), as shown to the right. And, C036=01

sets the relay to “normally closed” (relay coil

normally energized). The reason for this is that
a typical system design will require an inverter

power loss to assert an alarm signal to external

devices.

The relay can be used for other intelligent

output signals, such as the Run Signal (set

C026=00). For these remaining output signal
types, the relay coil typically must NOT change

state upon inverter power loss (set C036=00).

The figure to the right shows the relay settings
for the Run Signal output.

If you assign the relay an output signal

other than the Alarm Signal, the inverter
can still have an Alarm Signal output. In

this case, you can assign it to terminal

[11] , providing an open collector output.

AL1

AL0

AL2

Inverter logic
circuit board

AL1

AL0

AL2

Inverter logic
circuit board

C026=00

C036=00

Relay shown with inverter
power ON, Run Signal OFF

RUN

AL1

AL0

AL2

Inverter logic
circuit board

C026=05

C036=01

Relay shown with inverter
power ON, Alarm Signal OFF

AL