Ensure Adequate Ventilation

Step 2: To summarize the caution messages – you will need to find a solid, non-

flammable, vertical surface that is in a relatively clean and dry environment. In order to

ensure enough room for air circulation around the inverter to aid in cooling, maintain
the specified clearance and the inverter specified in the diagram.

CAUTION: Be sure to maintain the specified clearance area around the inverter and to
provide adequate ventilation. Otherwise, the inverter may overheat and cause

equipment damage or fire.

Keep Debris Out of Inverter Vents

Step 3: Before proceeding to the wiring section, it’s

a good time to

temporarily

covers the inverter’s

ventilation openings. Paper and masking tape are
all that is needed. This will prevent harmful debris

such as wire clippings and metal shavings from

entering the inverter during installation.

Please observe this checklist while mounting the

inverter:

1. The ambient temperature must be in the range

of

−10 to 40°C.

2. Keep any other heat-producing equipment as

far away from the inverter as possible.

3. When installing the inverter in an enclosure, maintain the clearance around the

inverter and verify that its ambient is within specification when the enclosure door

is closed.

4. Do not remove the front housing at any time during operation.

2

3

210

Inverter Mountin

g

and i

n

st

all

a

tio

n

Ventilation holes

(top)

Ventilation holes

(both sides)

Air flow

10 cm (3.94”)

minimum

10 cm (3.94”)

minimum

5 cm (1.97”)

minimum

5 cm (1.97”)

minimum

Clear area

X200

inverter