B − 37 – Hitachi X200 Series User Manual

Page 264

Advertising
background image

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

C044 PID deviation level

setting

R/W Sets the allowable PID loop error

magnitude (absolute value), SP-PV,

range is 0.0 to 100%, resolution is
0.1%

1129h 0 to 1000 0.1 %

C052 PID FBV function high

limit

R/W When the PV exceeds this value,

the PID loop turns OFF the PID
second stage output, range is 0.0 to

100%

112Eh 0 to 1000 0.1 %

C053 PID FBV function

variable low limit

R/W When the PV goes below this value,

the PID loop turns ON the PID

second stage output, range is 0.0 to
100%

112Fh 0 to 1000 0.1 %

C070 Selection of OPE /

ModBus

R/W Two option codes:

02

…OPE or option

03

…ModBus (485)

1137h

2, 3

C071 Communication speed

selection

1138h

C072 Node allocation

1139h

C074 Communication parity

selection

113Bh

C075 Communication stop bit

selection

113Ch

C076 Communication error

select

113Dh

C077 Communication error

time-out

113Eh

C078 Communication wait

time

NOTE: These network settings are
not accessible to ModBus. Use the

inverter keypad or digital operator

to edit. Refer to

“Network

Communication Settings” on page
3–60

.

113Fh

C081 O input span calibration R/W Scale factor between the external

frequency command on terminals
L–O (voltage input) and the

frequency output,

range is 0.0 to 200%

1141h 0 to 2000 0.1 %

C082 OI input span calibration R/W Scale factor between the external

frequency command on terminals

L–OI (voltage input) and the
frequency output,

range is 0.0 to 200%

1142h 0 to 2000 0.1 %

C086 AM offset calibration

R/W Offset adjustment of AM output.

Range is 0.0 to 10.0

Adjust together with B080 (AM
gain adjustment)

1145h 0 to 100

0.1 V

C091 Debug mode enable

Displays debug parameters.

Two option codes:
00

…Disable

01

…Enable

C101 Up/Down memory mode

selection

Controls speed setpoint for the

inverter after power sycle.

Two option codes:
00

…Clear last frequency (return to

default frequency F001)

01

…Keep last frequency adjusted

by UP/DWN

1149h

0, 1

B37

Appe

ndix B