Symptom/condition

Probable Cause

Solution

• If using the analog input, is the

current or voltage at [O] or [OI]?

• Check the wiring.
• Check the potentiometer or

signal generating device.

• Is the load too heavy?

• Reduce the load.

• Heavy loads activate the

overload restriction feature

(reduces output as needed).

The motor speed will not

reach the target frequency

(desired speed).

• Is the inverter internally limiting

the output frequency?

• Check max frequency setting

(A004)

• Check frequency upper limit

setting (A061)

The rotation is unstable

• Is the load fluctuation too great?

• Is the supply voltage unstable?

• Is the problem occurring at a

particular frequency?

• Increase the motor capacity

(both inverter and motor).

• Fix power supply problem.

• Change the output frequency

slightly, or use the jump
frequency setting to skip the

problem frequency.

The RPM of the motor does

not match the inverter

output frequency setting.

• Is the maximum frequency setting

A004 correct?

• Does the monitor function D001

display the expected output
frequency?

• Verify the V/f settings match

motor specifications.

• Make sure all scaling (such as

A011 to A014) is properly set.

• Was power turned OFF after a

parameter edit but before pressing
the Store key?

• Edit the data and press the

Store key once.

No download has
occurred

• Edits to data are permanently

stored at power down. Was the time
from power OFF to power ON less

than six seconds?

• Wait six seconds or more

before turning power OFF
after editing data.

Inverter

data us not

correct

The download

to the inverter

was attempted

• Was the power turned OFF within

six seconds after the display

changed from REMT to INV?

• Copy the data to the inverter

again, and keep power ON for

six seconds or more after

copying.

True for

certain
parameters

• Is the inverter in Run Mode? Some

parameters cannot be edited during
Run Mode.

• Put inverter in Stop Mode

(press the Stop/reset key).
Then edit the parameter.

A

parameter
will not

change

after an
edit

(reverts to

old

setting).

True for all
parameters

• If you’re using the [SFT] intelligent

input (software lock function)—is
the [SFT] input ON?

• Change the state of the SFT

input, and check the B031
parameter (SFT mode).