Hitachi X200 Series User Manual

Page 94

Advertising
background image

Frequency-related Functions

Frequency Limits – Upper and lower

limits can be imposed on the inverter
output frequency. These limits will

apply regardless of the source of the

speed reference. You can configure the
lower frequency limit to be greater than

zero as shown in the graph. The upper

limiter must not exceed the rating of the
motor or capability of the machinery.

The maximum frequency setting

(A004/A204) takes precedence over
frequency upper limit (A061/A261).

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA) Units

Frequency upper limit setting

A061

Lim H

0000.0Hz

Sets a limit on output frequency

less than the maximum

frequency (A004).

Range is from frequency lower
limit (A062) to maximum

frequency (A004).

0.0 setting is disabled
>0.0 setting is enabled

U

0.0

0.0

Hz

Frequency upper limit

setting, 2nd motor

A261

2Lim H

0000.0Hz

Sets a limit on output frequency

less than the maximum

frequency (A204).
Range is from frequency lower

limit (A262) to maximum

frequency (A204).
0.0 setting is disabled

>0.0 setting is enabled

U

0.0

0.0

Hz

Frequency lower limit setting

A062

Lim L

0000.0Hz

Sets a limit on output frequency

greater than zero.
Range is start frequency (B082)

to frequency upper limit (A061)

0.0 setting is disabled

>0.0 setting is enabled

U

0.0

0.0

Hz

Frequency lower limit

setting, 2nd motor

A262

2Lim L

0000.0Hz

Sets a limit on output frequency

greater than zero.

Range is start frequency (B082)
to frequency upper limit (A261)

0.0 setting is disabled

>0.0 setting is enabled

U

0.0

0.0

Hz

Output

frequency

A061

Upper

limit

Settable

range

A062

Lower

limit

Frequency command

0

320

Confi

guri

ng Driv

e

Parameters

Advertising