Operational Modes

The RUN and PRG LEDs tell just part of the story;

Run Mode and Program Modes are independent
modes, not opposite modes. In the state diagram to

the right, Run alternates with Stop, and Program

Mode alternates with Monitor Mode. This is a very
important ability, for it shows that a technician can

approach a running machine and change some

parameters without shutting down the machine.

The occurrence of a fault during operation will cause

the inverter to enter Trip Mode as shown. An event

such as an output overload will cause the inverter to
exit the Run Mode and turn OFF its output to the

motor. In the Trip Mode, any request to run the

motor is ignored. You must clear the error by
pressing the Stop/Reset switch. See “

Monitoring Trip

Events, History, & Conditions” on page 6-5

.

Run Mode Edit

The inverter can be in Run Mode (inverter output is controlling motor) and still allow
you to edit certain parameters. This is useful in applications that must run continuously,

you need some inverter parameter adjustment.

The parameter table in this chapter have a column titled “Run
Mode Edit”. An Ex mark

U

means the parameter cannot be

edited; a Check mark

9

means the parameter can be edited.

The Software Lock Setting (parameter B031) determines when
the Run Mode access permission is in effect and access

permission in other conditions, as well. It is the responsibility

of the user to choose a useful and safe software lock setting for
the inverter operating conditions and personnel. Please refer to

“Software Lock Mode” on page 3-36

for more information.

Control Algorithms

The motor control program in the X200
inverter has two sinusoidal PWM switching

algorithms. The intent is that you select the

best algorithm for the motor characteristics
in your application. Both algorithms generate

the frequency output in a unique way. Once

configured, the algorithm is the basis for
other parameter settings as well (see “

Torque

Control Algorithms” on page 3-16

). Therefore,

choose the best algorithm early in your
application design process.

Run

Stop

RUN

STOP

RESET

Monitor

Program

FUNC

Run

Stop

RUN

STOP

RESET

Trip

STOP
RESET

Fault

Fault

Run

Mode

Edit

U

9

Variable freq. control,

constant torque

Variable freq. control,

reduced torque

Output

Inverter Control Algorithms

35

Confi

guri

ng Driv

e

Parameters