Hitachi X200 Series User Manual

Page 115

Advertising
background image

“B” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA) Units

[AM] analog signal gain

B080

AM-Adj

00100%

Adjust of analog output at

terminal [AM],

range is 0 to 255

9

100.

100.

Start frequency adjustment

B082

fmin

0000.5Hz

Sets the starting frequency for
the inverter output, range is 0.5

to 9.9 Hz

U

0.5

0.5

Hz

Carrier frequency setting

B083

Carrier

0003.0

Sets the PWM carrier (internal
switching frequency), range is 2.0

to 12.0 kHz

U

3.0

3.0

kHz

Initialization mode

(parameters or trip history)

B084

INIT Mode

TRP

Select the type of initialization to

occur, three option codes:
00

…Trip history clear

01

…Parameter initialization

02

… Trip history clear and

parameter initialization

U

00

00

Country for initialization

B085

INIT Slct

EU

Select default parameter values

for country on initialization,
three option codes:
00

…Japan

01

…Europe

02

…US

U

01

02

Frequency scaling conversion
factor

B086

Cnv Gain

0001.0

Specify a constant to scale the
displayed frequency for D007

monitor, range is 0.1 to 99.9

9

1.0

1.0

STOP key enable

B087

STP Key

ON

Select whether the STOP key on

the keypad is enabled,

two option codes:
00

…Enabled

01

…Disabled

U

00

00

341

Confi

guri

ng Driv

e

Parameters