Automatic Voltage Regulation (AVR) Function

The automatic voltage regulation (AVR) feature keeps the inverter output waveform at

a relatively constant amplitude during power input fluctuations. This can be useful if
the installation is subject to input voltage fluctuations. However, the inverter cannot

boost its motor output to a voltage higher than the power input voltage. If you enable

this feature, be sure to select the proper voltage class setting for your motor.

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

AVR function select

A081

AVR Mode

ON

Automatic (output) voltage

regulation, selects from three
type of AVR functions, three

option codes:
00

…AVR enabled

01

…AVR disabled

02

…AVR enabled except during

deceleration

U

00

00

AVR voltage select

A082

AVR AC

00230V

200V class inverter settings:

……200/215/220/230/240
400V class inverter settings:

……380/400/415/440/460/480

U

230/

400

230/

460

V