Analog Signal Calibration Settings

The functions in the following table

configure the signals for the analog
input terminals. Note that these

settings do not change the

current/voltage or sink/source
characteristics – only the zero and

span (scaling) of the signals.

“C” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA) Units

O input span calibration

C081

O-ADJ

0100.0%

Scale factor between the external

frequency command on terminals

L–O (voltage input) and the
frequency output,

range is 0.0 to 200%

9

100.0 100.0

%

OI input span calibration

C082

OI-ADJ

0100.0%

Scale factor between the external

frequency command on terminals
L–OI (voltage input) and the

frequency output,

range is 0.0 to 200%

9

100.0 100.0

%

AM offset calibration

C086

AM OFFST

0000.0V

Offset adjustment of AM output.

Range is 0.0 to 10.0
Adjust together with B080 (AM

gain adjustment)

- See

page 3-40, 4-55

for details.

9

0.0

0.0

V

NOTE: When you restore factory default settings, the values will change to those listed
above. Be sure to manually reconfigure the values for your application, if needed, after

restoring factory defaults.