Circuit Breaker and Fuse Sizes

The inverter’s connections to input power for 400V class units must include UL Listed

inverse time circuit breakers with 600V rating, or UL Listed fuses as shown in the table
below.

Motor Output

Input

Voltage

kW

HP

Inverter Model

Fuse (A)

(UL-rated class J, 600V)

0.4

1/2

X200-004HFE/HFU

3

0.75

1

X200-007HFE/HFU

6

1.5

2

X200-015HFE/HFU

10

2.2

3

X200-022HFE/HFU

10

3.0

4

X200-030HFE

15

4.0

5

X200-040HFE/HFU

15

Three-

Phase

400V

Motor Overload Protection

Hitachi X200 inverters provide solid state motor overload protection, which depends on
the proper setting of the following parameters:

B012 “electronic overload protection”

B212 “electronic overload protection, 2nd motor”

Set the rated current [Amperes] of the motor(s) with the above parameters. The setting

range is 0.2 * rated current to 1.0 * rated current.

WARNING: When two or more motors are connected to the inverter, they cannot be
protected by the electronic overload protection. Install an external thermal relay on

each motor.