Troubleshooting Tips

The table below lists typical symptoms and the corresponding solution(s).

Symptom/condition

Probable Cause

Solution

• Is the frequency command source

A001 parameter setting correct?

• Is the Run command source A002

parameter setting correct?

• Make sure the parameter

setting A001 is correct

• Make sure the parameter

setting A002 is correct

• Is power being supplied to terminals

[L1], [L2], and [L3/N]? If so, the

POWER lamp should be ON.

• Check terminals [L1], [L2],

and [L3/N], then [U/T1],

[V/T2], and [W/T3].

• Turn ON the power supply or

check fuses.

• Is there an error code

E X X

displayed?

• Press the Func. key and

determine the error type.

Eliminate the error cause,

then clear the error (Reset).

• Are the signals to the intelligent

input terminals correct?

• Is the Run Command active?

• Is the [FW] terminal (or [RV])

connected to [PCS] (via switch, etc.)

• Verify the terminal functions

for C001–C005 are correct.

• Turn ON Run Command

enable.

• Supply 24V to [FW] or [RV]

terminal, if configured.

• Has the frequency setting for F001

been set greater than zero?

• Are the control circuit terminals

[H], [O], and [L] connected to the

potentiometer?

• Set the parameter for F001 to

a safe, non-zero value.

• If the potentiometer is the

frequency setting source,

verify voltage at [O] > 0V.

The inverter

outputs [U], [V],
[W] are not

supplying

voltage

• Is the RS (reset) function or FRS

(free-run stop) function ON?

• Turn OFF the command(s)

Inverter

outputs [U],

[V], [W] are
supplying

voltage.

• Is the motor load too heavy?

• Reduce the load, and test the

motor independently.

The motor

will not run

The optional

remote

operator is

used (SRW).

• Are the operational settings

between the remote operator and

the inverter unit correct?

• Check the operator type

setting.

• Are the connections of output

terminals [U/T1], [V/T2], and [W/T3]
correct?

• Is the phase sequence of the motor

forward or reverse with respect to

[U/T1], [V/T2], and [W/T3]?

• Make connections according to

the phase sequence of the
motor. In general:

FWD = U-V-W, and REV=U-

W-V.

The direction of the motor is

reversed

• Are the control terminals [FW] and

[RV] wired correctly?

• Is parameter F004 properly set?

• Use terminal [FW] for

forward, and [RV] for reverse.

• Set motor direction in F004.