Force Terminal Mode

The purpose of this intelligent input is to allow a device to force the inverter to allow

control of the following two parameters via the control terminals:

• A001 - Frequency source setting (01 = control terminals [FW] and [RV]

• A002 - Run command source setting (01 = control terminals [O] or [OI]

Some applications will require one or both settings above to use a source other than the
terminals. You may prefer to normally use the inverter’s keypad and potentiometer, or

to use the ModBus network for control, for example. However, an external device can

turn ON the [F-TM] input to force the inverter to (temporarily) allow control (frequency
source and Run command) via control terminals. When the [F-TM] input is OFF, then

the inverter uses the regular sources specified by A001 and A002 again.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Forces A001=01 (frequency source setting =

control terminal), and A002=01(Run command

source setting = control terminal)

51

F-TM

Force Terminal

Mode

OFF Inverter applies the user setting for A001 and

A002 normally

Valid for inputs:

C001~C005

Required settings

A001, A002

Notes:
• When changing the [F-TM] state during Run

Mode (inverter is driving the motor), the

inverter will stop the motor before the new [F-

TM] state takes effect.

Example (default input configuration shown—see

page 3–49

):

See I/O specs on

page 4–6.

Inverter Ready

The purpose of this intelligent input is to make inverter ready to start the motor

immediately when the RUN command is given. When the RDY input is active, motor

output terminal is active even if there is no RUN command.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Inverter is ready to act immediately when the

RUN command is given.

52

RDY

Inverter Ready

OFF Inverter performs normal start when the RUN

command is given.

Valid for inputs:

C001~C005

Required settings

A001, A002

Notes:

Example (default input configuration shown—see

page 3–49

):

See I/O specs on

page 4–6.

HIGH VOLTAGE: When set RDY function ON, there will be a voltage appear at

motor output terminals U, V and W even if the motor is in stop mode. So never touch
the inverter power terminal even the motor is not running.

5

4

3

2

1

L

PCS P24

F-TM

431

Operatio

ns and

Monitori

ng

5

4

3

2

1

L

PCS P24

RDY