External signal for dc braking – Hitachi X200 Series User Manual

Page 154

Advertising
background image

External Signal for DC Braking

When the terminal [DB] is turned ON, the

DC braking feature is enabled. Set the
following parameters when the external DC

braking terminal [DB] is to be used:

• A053 – DC braking delay time setting.

The range is 0.1 to 5.0 seconds.

• A054 – DC braking force setting. The

range is 0 to 100%.

The scenarios to the right help show how DC

braking works in various situations.

1. Scenario 1 – The [FW] or [RV] terminal is

ON. When [DB] is ON, DC braking is

applied. When [DB] is OFF again, the
output frequency ramps to the prior level.

2. Scenario 2 – The Run command is applied

from the operator keypad. When the [DB]
terminal is ON, DC braking is applied.

When the [DB] terminal is OFF again, the

inverter output remains OFF.

3. Scenario 3 – The Run command is applied

from the operator keypad. When the [DB]

terminal is ON, DC braking is applied
after the delay time set by A053 expires.

The motor is in a free-running (coasting)

condition. When the [DB] terminal is OFF
again, the inverter output remains OFF.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Applies DC injection braking during deceleration

07

DB

External DC
Braking

OFF Does not apply DC injection braking during

deceleration

Valid for inputs:

C001~C005

Required settings

A053, A054

Notes:
• Do not use the [DB] input continuously or for a

long time when the DC braking force setting

A054 is high (depends on the motor application).

• Do not use the [DB] feature for continuous or

high duty cycle as a holding brake. The [DB]

input is designed to improve stopping

performance. Use a mechanical brake for
holding a stop position.

Example (requires input configuration—see

page 3–49

):

See I/O specs on

page 4–6.

5

4

3

2

1

L

PCS P24

DB

[FW,RV]

1

0

[DB]

1

0

Output
frequency

Scenario 1

t

Run command
from operator

1

0

[DB]

1

0

Output
frequency

Scenario 2

t

Run command
from operator

1

0

[DB]

1

0

Output
frequency

Scenario 3

t

delay

A053

415

Operatio

ns and

Monitori

ng