B − 26 – Hitachi X200 Series User Manual

Page 253

Advertising
background image

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

A020 Multi-speed 0 setting

R/W Defines the first speed of a

multi-speed profile, range is 0.0 /

start frequency to 400 Hz
A020 = Speed 0 (1st motor)

1029h

0 / start

freq. to

4000

0.1 Hz

A220 Multi-speed 0 setting

2nd motor

R/W Defines the first speed of a

multi-speed profile, range is 0.0 /
start frequency to 400 Hz

A220 = Speed 0 (2nd motor)

150Fh

0 / start

freq. to

4000

0.1 Hz

A021 Multi-speed 1 setting

R/W

102Bh

A022 Multi-speed 2 setting

R/W

102Dh

A023 Multi-speed 3 setting

R/W

102Fh

A024 Multi-speed 4 setting

R/W

1031h

A025 Multi-speed 5 setting

R/W

1033h

A026 Multi-speed 6 setting

R/W

1035h

A027 Multi-speed 7 setting

R/W

1037h

A028 Multi-speed 8 setting

R/W

1039h

A029 Multi-speed 9 setting

R/W

103Bh

A030 Multi-speed 10 setting R/W

103Dh

A031

Multi-speed 11 setting R/W

103Fh

A032

Multi-speed 12 setting R/W

1041h

A033

Multi-speed 13 setting R/W

1043h

A034

Multi-speed 14 setting R/W

1045h

A035

Multi-speed 15 setting R/W

Defines 15 more speeds,

range is 0.0 / start frequency to

400 Hz.

A021= Speed 1...

A035 = Speed 15

1047h

0 / start

freq. to

4000

0.1 Hz

A038

Jog frequency setting

R/W Defines limited speed for jog,

range is 0.00 / start frequency
to 9.99 Hz

1048h

0 / start

freq. to

999

0.01 Hz

A039

Jog stop mode

R/W

Define how end of jog stops

the motor; three options:

00...Free-run stop

01...Controlled deceleration
02...DC braking to stop

1049h

0, 1, 2

A041

Torque boost select

R/W

104Ah

A241

Torque boost select,

2nd motor

R/W

Two options:

00...Manual torque boost
01...Automatic torque boost

1510h

0, 1

A042

Manual torque boost

value

R/W

104Bh

A242 Manual torque boost

value, 2nd motor

R/W

Can boost starting torque

between 0 and 20% above normal

V/f curve,
range is 0.0 to 20.0%

1511h

0 to 200

0.1 %

A043 Manual torque boost

frequency adjustment

R/W

104Ch

A243 Manual torque boost

frequency adjustment,

2nd motor

R/W

Sets the frequency of the V/f

breakpoint A in graph (top of

previous page) for torque boost,
range is 0.0 to 50.0%

1512h

0 to 500

0.1 %

A044 V/f characteristic curve

selection

R/W

104Dh

A244 V/f characteristic curve

selection, 2nd motor

R/W

Two available V/f curves;

two select codes:

00...Constant torque
01...Reduced torque

06...Reduced torque1

1513h

0, 1, 6

A045 V/f gain setting

R/W

104Eh

A245 V/f gain setting, 2nd

motor

R/W

Sets voltage gain of the inverter,

range is 20. to 100.%

1514h

20 to 100

1 %