Connecting the Inverter to ModBus

Follow these steps in this section to connect the inverter to the ModBus network.

1. Open Serial Port Cover - The inverter keypad has a hinged dust cover protecting the

serial port connector. Lift the cover from the bottom edge, and tilt upward as shown

below.

2. Modular Interconnect Removal - With the serial port cover opened, notice the RJ45

modular connector behind it. Connect the serial cable and engage the locking tab in

the connector.

3. Cable Wiring - The inverter communications

port uses RS485 differential transceiver. The

pinout is shown to the right and listed below.

Be sure the cable connection you make
matches the diagram.

Pin

Symbol

Description

1

Not used. Do not connect

2

Not used. Do not connect

3

Not used. Do not connect

4

L

Common

5

SP

Send data positive

6

SN

Send data negative

7

L

Common

8

Not used. Do not connect

B3

Appe

ndix B

RJ45 connector

1 2 3 4 5 6 7 8