Potentiometer Settings

Input Range Settings – The parameters in the following table adjust the input

characteristics of the integrated POT. When using the POT to command the inverter
output frequency, these parameters adjust the starting and ending ranges for the POT,

as well as the output frequency range.

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA) Units

POT active range start

frequency

A151

POT-EXS

0000.0Hz

The output frequency

corresponding to the POT range

starting point,
range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

POT input active range end

frequency

A152

POT-EXE

0000.0Hz

The output frequency

corresponding to the POT range
ending point,

range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

POT input active range start

A153

POT-EX%S

00000%

The starting point (offset) for the

POT range,

range is 0. to 100.%

U

0.

0.

%

POT input active range end

A154

POT-EX%E

00000%

The ending point (offset) for the

POT range,

range is 0. to 100.%

U

100.

100.

%

POT input start frequency

enable

A155

POT-LVL

0Hz

Two options; select codes:
00

…Use offset (A151 value)

01

…Use 0Hz

U

01

01

Max frequency

A152

A151

A154

100%

Counterclockwise

Clockwise

A153

0%

A015=00

A015=01

0

Input scale

%

331

Confi

guri

ng Driv

e

Parameters