Output Function Adjustment Parameters

The following parameters work in

conjunction with the intelligent output
function, when configured. The overload

level parameter (C041) sets the motor

current level at which the overload signal
[OL] turns ON. The range of setting is

from 0% to 200% of the rated current for

the inverter. This function is for
generating an early warning logic output,

without causing either a trip event or a

restriction of the motor current (those
effects are available on other functions).

The frequency arrival signal, [FA1] or

[FA2], is intended to indicate when the
inverter output has reached (arrived at)

the target frequency. You can adjust the

timing of the leading and trailing edges of
the signal via two parameters specified to

acceleration ad deceleration ramps, C042

and C043.

The Error for the PID loop is the

magnitude (absolute value) of the
difference between the Set point (desired

value) and Process Variable (actual

value). The PID output deviation signal
[OD] (output terminal function option

code 04) indicates when the error

magnitude has exceeded a magnitude you
define.

Output
freq.

C042

C043

[FA2]
output

1
0

t

t

C041

Output
current

[OL]
output

0

1
0

t

t

t

C044

[OD]
output

1
0

t

Output

PID Error (PV-SP) deviation threshold

358