WARNING: Rotating shafts and above-ground electrical potentials can be hazardous.
Therefore, it is strongly recommended that all electrical work conform to the National
Electrical Codes and local regulations. Installation, alignment and maintenance should

be performed only by qualified personnel.

CAUTION:
a) Class I motor must be connected to earth ground via low resistive path (<0.1

Ω)

b) Any motor used must be of a suitable rating.

c) Motors may have hazardous moving path. In this event suitable protection must be

provided.

CAUTION: Alarm connection may contain hazardous live voltage even when inverter is
disconnected. When removing the front cover for maintenance or inspection, confirm

that incoming power for alarm connection is completely disconnected.

CAUTION: Hazardous (main) terminals for any interconnection (motor, contact
breaker, filter, etc.) must be inaccessible in the final installation.

CAUTION: This equipment should be installed in IP54 or equivalent (see EN60529)
enclosure. The end application must be in accordance with BS EN60204-1. Refer to the

section “Choosing a Mounting Location” on page 2-9. The diagram dimensions are to be

suitably amended for your application.

CAUTION: Connection to field wiring terminals must be reliably fixed having two
independent means of mechanical support. Use a termination with cable support

(figure below), or strain relief, cable clamp, etc.

CAUTION: A double-pole disconnection device must be fitted to the incoming main
power supply close to the inverter. Additionally, a protection device meet IEC947-1/

IEC947-3 must be fitted at this point (protection device data shown in “Determining

Wire and Fuse Sizes” on page 2-17).

NOTE: The above instructions, together with any other requirements highlighted in

this manual, must be followed for continue LVD (European Low Voltage Directive)
compliance.