List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

B133 DC bus AVR

selection

R/W Two option codes:

00

…Disabled

01

…Enabled

1176h

0, 1

B134 Threshold voltage of

DC bus AVR setting

R/W Setting of threshold voltage of DC bus

voltage to start DC bus AVR function.

Range is:
200V class

…330 to 395

400V class

…660 to 790

1177h 330 to 395,

660 to 790

1 V

B140 Over-current trip

suppression

R/W Two option codes:

00

…Disable

01

…Enable

10F7h

0, 1

B150 Carrier mode

R/W Automatically reduces the carrier

frequency as the ambient temperature

increases.
00

…Disable

01

…Enable

10F8h

0, 1

B151 Selection of RDY

function

R/W Select Ready function.

00

…Disable

01

…Enable

10F9h

0, 1

Note 1: