Frequency Arrival Signals

The

Frequency Arrival

group of outputs help coordinate external systems with the

current velocity profile of the inverter. As the name implies, output [FA1] turns ON
when the output

frequency arrives

at the standard set frequency (parameter F001).

Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility.

For example, you can have an output turn ON at one frequency during acceleration, and
have it turn OFF at a different frequency during deceleration. All transitions have

hysteresis to avoid output chatter if the output frequency is near one of the thresholds.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

when output to motor is at the set frequency

01

FA1

Frequency Arrival

Type 1 – Constant

Speed

OFF when output to motor is OFF, or in any

acceleration or deceleration ramp

ON

when output to motor is at or above the set

frequency thresholds for, even if in acceleration or

deceleration ramps

02

FA2

Frequency Arrival

Type 2 – Over

frequency

OFF when output to motor is OFF, or during

acceleration or deceleration before the respective
thresholds are crossed

Valid for inputs:

11, AL0 – AL2

Required settings

(none)

Notes:
• For most applications you will need to use only

one type of frequency arrival outputs (see

examples). However, it is possible assign both

output terminals to output functions [FA1] and
[FA2].

• For each frequency arrival threshold, the output

anticipates the threshold (turns ON early) by

1.5Hz.

• The output turns OFF as the output frequency

moves away from the threshold, delayed by

0.5Hz.

• The delay time of the output signal is 60 ms

(nominal).

• The example circuit for terminal [11] drives a

relay coil. Note the use of a diode to prevent the

negative going turn-off spike generated by the
coil from damaging the inverter’s output

transistor.

Example for terminal [11] (default output
configuration shown – see page 3-54):

Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see

page 54

):

See I/O specs on

page 4-6

RY

Inverter output
terminal circuit

CM2

11

FA1

AL1

Power
supply

Load

AL0

AL2

Inverter logic
circuit board

FA1

438