Hitachi X200 Series User Manual

Page 92

Advertising
background image

DC Braking (DB) Settings

Normal DC braking performance

⎯ The DC

braking feature can provide additional

stopping torque when compared to a normal
deceleration to a stop. DC braking is

particularly useful at low speeds when

normal deceleration torque is minimal. When
you enable DC braking, the inverter injects a

DC voltage into the motor windings during

deceleration below a frequency you can
specify (A052).

The braking power (A054) and duration (A055) can both be set. You can optionally

specify a wait time before DC braking (A053), during which the motor will free run.

DC Braking – Frequency Detection

⎯ All above operations are done when the RUN

command (FW signal) turns OFF. But you can even set DC braking during Run by

setting

frequency detection

at A051. In this case the DC brake operates when the output

frequency comes down to the one you specified (A052) even the Run command is active.

External DB and Internal DC are invalid during the frequency detection mode.

Example 1, above to the left shows the performance when giving the pulsing frequency

set point. In this case, when changing set point to 0, inverter immediately starts DB

because the set point becomes lower than the value specified in A052. And the DB
continues until the set point exceeds A052. And there will be no DC braking at next stop

because the FW is being OFF.

Example 2, above to the right shows the gradual change in frequency set point, for
example by analog input. In this case, there will be a DC braking period at start

because the frequency set point is lower than the value specified in A052.

Running

DC brake

Free run

+

0

-

t

A053

A055

FW

ON

F-SET

A052

DB

Ex.1) Step change in F-SET.

F-OUT

FW

ON

F-SET

A052

Ex.2) Analog change in F-SET.

F-OUT

DB

DB

DB

318

Confi

guri

ng Driv

e

Parameters

Advertising