Analog Input Current/Voltage Select

The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI]

input terminals for external frequency control. When intelligent input [AT] is ON, you
can set the output frequency by applying a current input signal at [OI]-[L]. When the

[AT] input is OFF, you can apply a voltage input signal at [O]-[L] to set the output

frequency. Note that you must also set parameter A001 = 01 to enable the analog
terminal set for controlling the inverter frequency.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

16

AT

Analog Input
Voltage/Current

Select

OFF

See the table down below

Valid for inputs:

C001~C005

Required settings

A001 = 01

Notes:

• If the [AT] option is not assigned to any

intelligent input terminal, then inverter

recognizes [AT] = OFF in following table.

• Be sure to set the frequency source setting

A001=01 to select the analog input terminals.

Example (default input configuration shown
for –FU models; –FE models require input
configuration—see

page 3–49

):

See I/O specs on

page 4–6.

Combination of A005 setting and [AT] input for analog input activation.

A005

[AT] Input

Analog Input Configuration

ON

Keypad Pot

02

OFF

[O]

ON

Keypad Pot

03

OFF

[OI]

04

(ignored)

[O]

05

(ignored)

[OI]

Note that you cannot give [O] and [OI] input at the same time on X200 inverter.