B − 16 – Hitachi X200 Series User Manual

Page 243

Advertising
background image

Write in Holding Registers [10h]:

This function writes data in consecutive holding registers. An example follows:
• Write “3000 seconds” as the first acceleration time 1 (F002) in an inverter having a

slave address “8.”

• This example uses change data “300000(493E0h)” to set “3000 seconds” as the data

resolution of the registers “1014h” and “1015h” holding the first acceleration time 1

(F002) is 0.01 second.

Query:

Response:

No.

Field Name

Example

(Hex)

No.

Field Name

Example

(Hex)

1

Slave address *1

08

1

Slave address

08

2

Function code

10

2

Function code

10

3

Start address *3

(high order)

10

3

Start address *3

(high order)

10

4

Start address *3

(low order)

13

4

Start address *3

(low order)

13

5

Number of holding

registers (high order)

00

5

Number of holding

registers (high order)

00

6

Number of holding

registers (low order)

02

6

Number of holding

registers (low order)

02

7

Byte number *2

04

7

CRC-16 (high order)

B4

8

Change data 1
(high order)

00

8

CRC-16 (low order)

54

9

Change data 1

(low order)

04

10

Change data 2

(high order)

93

11

Change data 2

(low order)

E0

12

CRC-16 (high order)

7D

13

CRC-16 (low order)

53

Note 1:

Broadcasting is disabled.

Note 2:

This is not the number of holding registers. Specify the number of bytes of
data to be changed.

Note 3:

The PDU Register Number are addressed starting at zero. Therefore register

numbered “1014h” are addressed as “1013h”. Register address value
(transmitted on Modbus line) is 1 less than the Register Number.

When writing in selected holding registers fails, see the exception response.

B16

Appe

ndix B

Advertising